background image

Manual

2100-435D

Page

9 of 38

HANDLING UNIT AFTER REMOVAL
FROM SKID

FIGURE  4

UNIT ON APPLIANCE CART

The unit will have to be turned sideways and removed
from the skid to fit through a 36" doorway.  If the door
height allows, the unit can be slid sideways through the
door.

If the unit can not be slid through the door, then the unit
will have to be put on a cart and tipped down to roll
through the door.  It is recommended that an appliance
cart by used with a strap to hold the unit on the cart.

The wheels of the unit 

must be locked

.  If the wheels

were allowed to roll, the unit could roll off the cart.  

The

unit should always be carted from the left side

.  This is

the side where the compressor is located.  See Figure 4.
The blade of the appliance cart should be slid under the
wheels of the unit.  The strap of the appliance cart
should be placed around the unit and strapped tightly.
Help will be required to tip the unit back onto the cart.
The unit can be leaned far enough back to be rolled
through the door.  Be careful when setting the unit back
up to keep from damaging the unit.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Systems of
Other Than Residence Type, NFPA No. 90A, and
Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

MINIMUM INSTALLATION HEIGHT

The minimum installation height of the unit with a Free
Blow Plenum is 8 ft. 6 in.  This provides enough
clearance for the plenum to be removed.  See Figure 5.

The minimum installation height for ducted applications
is 8 ft. 4½ in.  This provides enough clearance to install
the duct work.  See Figure 6.

        WARNING

Exercise extreme caution when pushing the
unit on the rollers.  Handle and push from the
lower 1/3 of the unit.  Insure that debris is not
on the floor where the unit is to be moved on
the rollers.  Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.

QT

EC

 UNIT

(Right Side)

APPLIANCE

CART

COMPRESSOR

MIS-1555

STRAP

Summary of Contents for QTEC QH303D

Page 1: ...QH423D QH483D QH603D QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 435D Supersedes 2100 435C...

Page 2: ...ation 23 Service Hints 24 Mist Eliminator Service 24 Vent Options 25 Sequence of Operation 28 Optional Climate Controls Sequence of Operation 28 Refrigerant Tube Schematic for Reheat Coil 29 Pressure...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...otorized w Exhaust Spring Return FILTER OPTIONS X 1 Inch Fiberglass Standard F 2 Inch Fiberglass P 2 Inch Pleated COLOR OPTIONS V Platinum w Slate Front Vinyl 4 Gray paint TABLE 1 FACTORY BUILT IN ELE...

Page 5: ...R E W O P E R I W E Z I S 2 D N U O R G E R I W E Z I S 3 M U M I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z...

Page 6: ...Z 0 B D 3 8 4 H Q 6 0 B D 9 0 B D 5 5 1 B D 3 8 0 2 0 3 2 1 1 1 1 6 2 4 4 3 5 3 5 0 4 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C D 3 8 4 H Q 6 0 C D 9 0 C D 5 5 1 C D 3 0 6 4 1 1 1 1 4 1 3 2 7 2 7 2 5...

Page 7: ...Manual 2100 435D Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...

Page 8: ...e removed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge...

Page 9: ...ructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and an...

Page 10: ...NG 8 FT 6 IN MINIMUM RECOMMENDED CEILING HEIGHT 8 FT 5 IN FLOOR MIS 1573 SUSPENDED CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIM...

Page 11: ...free blow with the use of QPB Plenum Box or a duct supply air system For hot water coil options a QPBHW F for free blow or QPBHW D for ducted airflow is used The QPB and QPBHW Plenum Box mounts on top...

Page 12: ...nnections on the unit The rear drain is the primary drain and is located on the right lower rear panel of the unit The optional side drain is located on the bottom right side of the unit The side drai...

Page 13: ...ice This indicates that the unit needs to be serviced MIS 1061 FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PA...

Page 14: ...keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel o...

Page 15: ...that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable...

Page 16: ...under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing the Y compressor signal alone turns the compressor off but does not activa...

Page 17: ...S s e r u t a e F t n a n i m o d e r P 8 1 0 3 0 4 8 4 2 0 1 N 4 7 8 T 0 1 0 4 0 4 8 1 6 2 1 4 7 6 Q 2 l o o C t a e H c i t a m o t u A n o i t i s o P r e v o e g n a h C 8 3 0 3 0 4 8 A 0 0 6 H A...

Page 18: ...3 4 5 6 7 8 9 10 11 12 Y1 G E 7 6 5 4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 W1 Y1 W1 L C R W2 L C R W2 B B E1 G A1 Y1 4 3 5 6 Y G O1 4 E 5 6 Blue Red Red Yellow Tan Orange Yellow Blue Br...

Page 19: ...ns to control ventilation must be used if any of the mechanical motorized ventilation options are installed DEHUM CIRCUIT 24 VAC COM DEHUM CIRCUIT COMPRESSOR NOTE FIELD SUPPLIED DEHUMIDISTAT MUST BE D...

Page 20: ...n Blue Yellow Orange Tan Orange Red Red Red Red Black Black Black Red 2 3 1 2 3 4 5 6 7 8 9 10 11 12 7 6 5 4 3 2 1 Plug 4 8 12 11 10 9 Brown Blue W1 L C R W2 B E1 G A1 Y1 Blue Red Red Tan Orange Yello...

Page 21: ...n Blue Yellow Orange Tan Orange Red Red Red Red Black Black Black Red 2 3 1 2 3 4 5 6 7 8 9 10 11 12 Y1 G 7 6 5 4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 4 3 5 6 Blue Red Red Yellow Tan Ora...

Page 22: ...4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 4 3 5 6 Blue Red Red Yellow Tan Orange Yellow Blue Brown Red Black H200 Humidistat T8511 Thermostat Yellow E C Y1 Y O1 Terminal Block 1 Black Red...

Page 23: ...nitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED w...

Page 24: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Page 25: ...h the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed QTEC R ENERGY RECOVERY VENTILATOR Option Before starti...

Page 26: ...Manual 2100 435D Page 26 of 38 MIS 1627 FIGURE 17 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 27: ...Manual 2100 435D Page 27 of 38 MIS 1039 FIGURE 18 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 28: ...ion can be restored by turning of the main power supply off and then back on or reset the room thermostat The low pressure control has a bypass to eliminate nuisance lockout on cold start up The bypas...

Page 29: ...humidity is above the setpoint of the humidistat the compressor circuit and the 3 way valve are energized and the evaporator air flow is reduced The 3 way valve directs hot discharge gas into a separa...

Page 30: ...Manual 2100 435D Page 30 of 38 FIGURE 20 QTEC DEHUMIDIFICATION MODE CIRCUIT DIAGRAM MIS 1088...

Page 31: ...Manual 2100 435D Page 31 of 38 FIGURE 21 QTEC COOLING MODE CIRCUIT DIAGRAM MIS 1089...

Page 32: ...a 0 coil temperature This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region Use a small screwdriver or other metallic object o...

Page 33: ...p a c d e t r o h s r o n e p o r o t i c a p a c e c a l p e R l o r t n o c p m u p t a e H e v i t c e f e d t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p C N m o C l o r...

Page 34: ...3 9 8 0 0 1 9 9 3 1 8 8 1 7 3 5 8 9 9 6 2 8 1 2 1 0 8 2 3 6 7 7 0 3 2 5 7 0 1 9 2 7 0 7 6 0 7 7 0 5 8 6 8 1 4 6 6 9 9 3 4 6 9 4 4 2 6 5 6 5 0 6 5 4 7 8 5 0 3 1 0 4 1 0 5 1 0 6 1 0 7 1 0 8 1 0 9 1 0 0...

Page 35: ...ing performance will occur with a refrigerant charge resulting in a Super Heat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating...

Page 36: ...L e d i S h g i H 4 7 2 1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8...

Page 37: ...2 2 3 6 3 H Q g e d 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 7 2 7 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9 1 2 5 2 0 2 5 5 6 0 2 9 5 1 1 2 3 6 7 1 2 3 2 4...

Page 38: ...a jumper on it to choose between fulltime dehumidification and occupied dehumidification only With the jumper in the 1 2 position dehumidification is available fulltime With the jumper in the 2 3 posi...

Reviews: