background image

Manual

2100-319F

Page

7 of 10

FIGURE  5

TYPICAL INSTALLATION WITH 14" MAX. WALL THICKNESS

sealant must be applied as required.  The sleeve must be
anchored to the wall.  All four mounting flanges must be
fastened with two fasteners each to the outside wall.
The gaps between the side flanges, and the top and
bottom flanges must be sealed to the wall.

On the inside of the building, the gaps between the
sleeve and the opening must be filled with insulation.
This will help insulate the sleeve and prevent infiltration
of any unwanted outdoor air.  See Figure 5.

If the QT

EC

 unit will be drained through the wall, the

drain line must be installed through the wall.
Information for the drain installation is contained in the
QT

EC

 Installation Instructions.

square in the opening.  A slope is built into the bottom of
the sleeve from the inside to the outside.  This will allow
any water that gets into the sleeve to drain out.  Once the
test fitting has been checked out, the sleeve should be
removed from the wall.

With the sleeve removed, two 1/4 inch beads of sealant
must be applied to the flanges that contact the outside
wall.  See Figure 3

The sleeve must be installed back in the wall making
sure that the predrilled holes in the wall line up with the
holes in the mounting flanges of the sleeve.  Check to
make sure that there is enough sealant between the wall
and the flanges to make the joint watertight.  Additional

INSIDE
WALL

WALL BRACKET

QTEC UNIT

OUTSIDE WALL

INSULATION

OUTDOOR GRILLE

CONDENSER COIL AND FAN
INSERTED INTO SLEEVE

WALL BRACKET

INSULATION

TOP SECTION VIEW

Summary of Contents for QWS48A QWS48A-16

Page 1: ...l No 2100 319F Supersedes 2110 319E File Vol II Tab 14 Date 11 07 05 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned QTEC Wall Sleeve Models QWS48A QWS48A 16 QWS48A...

Page 2: ...llation with 23 Thick Walls 8 Installation with 30 Thick Walls 8 Accessory Item QCDS48 Condensate Disposal System 9 Attachment of Wall Sleeve to Unit 10 Figures Figure 1 Wood Framed Installation 4 Fig...

Page 3: ...g Systems QTEC Installation Instruction Manual Bard 2100 288 FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009...

Page 4: ...er studs to support the header and to provide a structural member on which to fasten the sleeve See Figure 1 All of the dimensions are referenced from the finished floor height After the opening is fr...

Page 5: ...SEALANT TO FLANGES FIGURE 2 APPLICATION OF SEALANT TO 2 X 6 PLATE FRONT VIEW SLEEVE OPENING TREATED 2 X 6 BOTTOM SUPPORTAND SEAL PLATE APPLY CONSTRUCTION ADHESIVE TO SEAL APPLY CONSTRUCTIONADHESIVE TO...

Page 6: ...ll Information for the drain installation is contained in the QTEC Installation Instructions FIGURE 4 MASONRYCONSTRUCTIONINSTALLATION INSTALLATION MASONRY CONSTRUCTION WALLS For masonry construction w...

Page 7: ...stallation is contained in the QTEC Installation Instructions square in the opening A slope is built into the bottom of the sleeve from the inside to the outside This will allow any water that gets in...

Page 8: ...plate and secure with the three screws INSTALLATION WITH 23 THICK WALLS When an application is required on a building with 23 wall a Wall Sleeve model number QWS48A 23 is required The installation of...

Page 9: ...attaches to the side of the sleeve The drain box has a rear drain and an overflow The rear drain assembly installs in the rear drain of the QTEC This system allows the QTEC unit to be installed or rem...

Page 10: ...re there is not adequate clearance to drive the screws into the cabinet sides The attachment can be made from inside the unit There are two threaded studs extending from the room side of the sleeve to...

Reviews: