8.
MOUNTING THE UNIT
1. These units are secured by wall mounting
brackets which secure the unit to the outside
wall surface at both sides. A bottom mounting
bracket is provided for ease of installation but
is not required.
2.
The W42G, W48G and W60G models are
suitable for 0 inch clearance on the installation
mounting wall and to the top. For all models the
supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1-inch
clearance to combustible material. The W24G,
W30G and W36G models are suitable for 0 inch
clearance on the installation mounting wall, but
require 1-inch clearance to the top if combustible
material overhang projects above the unit. See
Figure 3 and 3A. If a combustible wall, use a
minimum of Figure 1 “A” dimension plus 2
inches and “B” dimension plus 2 inches. See
Figures 4 and 5 for details.
3. Locate and mark lag bolt locations and bottom
mounting bracket location.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top.
Top rain flashing is shipped secured to the right
side of the back.
6. Position unit in opening and secure with 5/16
lag bolts; use 7/8 inch diameter flat washers on
the lag bolts. Use lag bolts long enough to
support the unit’s weight when mounted to the
structure. This length may be dependant on the
type of construction.
7. Secure rain flashing to wall and caulk across
entire length of top. See Figure 3.
8. On side-by-side installations, maintain a
minimum of 20 inches clearance on right side
to allow access to control panel and burner
compartment, and to allow proper airflow to the
outdoor coil. Additional clearance may be
required to meet local or national codes.
4.
HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on sea
level operation and need not be changed for operation at
elevations up to 6,000 feet. For operation at elevations
above 6,000 feet and in the absence of specific
recommendations from the local authority having
jurisdiction, equipment ratings shall be reduced as
specified in Section 21.
5.
TRANSPORTATION DAMAGE
All units are packed securely in shipping container. All
units should be carefully inspected upon arrival for
damage. In the event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notified as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be filed with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certified copy, or
indemnity bond.
B. Original paid freight bill of indemnity in lieu thereof.
C. Original invoice or certified copy thereof showing
trade and other discounts or deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
6. INSTALLATION
Size of unit for proposed installation should be based on
heat loss/heat gain calculations made according to
methods of Air Conditioning Contractors of America
(ACCA). The air duct should be installed in accordance
with the Standards of the National Fire Protection
Association for the Installation of Air Conditioning and
Ventilating Systems of Other Than Residence Type,
NFPA No. 90A, and Residence Type Warm Air Heating
and Air Conditioning Systems, NFPA No. 90B. Where
local regulations are at a variance with instructions,
installer should adhere to local codes.
7.
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air
openings must be cut through the wall as
detailed in Figure 4.
2. On wood-frame walls, the wall construction
must be strong and rigid enough to carry the
weight of the unit without transmitting any unit
vibration.
3. Concrete block walls must be thoroughly
inspected to insure that they are capable of
carrying the weight of the installed unit.
CAUTION
If the bottom bracket is used, be certain the
bracket is secured to the outside wall surface
in a way sufficient to support the entire weight
of the unit during installation until side
mounting brackets are secured.
WARNING
Failure to provide the one inch clearance
between the supply duct and a combustible
surface for the first three feet of duct can
result in fire causing damage, injury or death.
Summary of Contents for W24G2-A
Page 13: ...Manual 2100 590A Page 13 of 67 FIGURE 2A MOUNTING INSTRUCTIONS FOR W42G W48G AND W60G ...
Page 16: ...Manual 2100 590A Page 16 of 67 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...
Page 25: ...Manual 2100 590A Page 25 of 67 FIGURE 14 GAS PIPE CONNECTION W24G W36G W42G W60G ...
Page 51: ...Manual 2100 590A Page 51 of 67 W24G2 A 230 208 60 1 ...
Page 53: ...Manual 2100 590A Page 53 of 67 W24G2 B 230 208 60 3 ...
Page 55: ...Manual 2100 590A Page 55 of 67 W24G2 C 460 60 3 ...
Page 57: ...Manual 2100 590A Page 57 of 67 W30G2 A W36G2 A W42G2 A W48G2 A 230 208 60 1 ...
Page 59: ...Manual 2100 590A Page 59 of 67 W30G2 B W36G2 B W42G2 B W48G2 B 230 208 60 3 ...
Page 61: ...Manual 2100 590A Page 61 of 67 W30G2 C W36G2 C W42G2 C W48G2 C 460 60 3 ...
Page 63: ...Manual 2100 590A Page 63 of 67 W60G2 A 230 208 60 1 ...
Page 65: ...Manual 2100 590A Page 65 of 67 W60G2 B 230 208 60 3 ...
Page 67: ...Manual 2100 590A Page 67 of 67 W60G2 C 460 60 3 ...