FIGURE 3
COMBUSTIBLE CLEARANCE
FOR WF MODELS
WARNING
A
minimum
of one (1) inch clearance must be maintained between the supply air duct and combustible materials.
This is required for the first three (3) feet of ducting.
It is important to insure that the one (1) inch minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a fire causing damage,
injury or death.