Manual 2100-365
Page 21
8. Refer to Table 6 for Gas Pipe Sizes for natural gas.
If more than one appliance is supplied from a single
line size, capacity must equal or exceed the
combined input to all appliances, and the branch
lines feeding the individual appliances properly
sized for each input.
4. An 1/8” NPT plugged tapping accessible for test
gauge connection shall be installed immediately
upstream of the gas supply connection to the furnace
for the purpose of determining the supply gas
pressure. This can be omitted if local codes permit
use of plugged tapping in gas valve inlet.
5. Install listed manual shutoff valve in the supply gas
line external to and immediately upstream of the
furnace. See Figure 12.
6. Use steel or wrought iron pipe and fittings.
7. DO NOT thread pipe too far. Valve distortion or
malfunction may result from excess pipe within the
control. Use pipe joint compound resistant to the
action of liquefied petroleum gases on male threads
only. DO NOT use Teflon tape. See Table 5 and
Figure 13.
18. GAS SUPPLY AND PIPING
GENERAL RECOMMENDATIONS
1. Be sure the gas line complies with the local codes
and ordinances, or in their absence with the National
Fuel Gas Code, ANSI Z223.1, or Natural Gas
Installation Code, CAN/CGA B149.1, or Propane
Installation Code B149.2, latest edition.
2. A sediment trap or drip leg must be installed in the
supply line to the furnace.
3. A ground joint union shall be installed in the gas line
adjacent to and upstream from the gas valve and
downstream from the manual shutoff valve.
TABLE 5
LENGTH OF STANDARD
PIPE THREADS (INCHES)
e
z
i
S
e
p
i
P
h
t
g
n
e
L
e
v
i
t
c
e
f
f
E
d
a
e
r
h
T
f
o
h
t
g
n
e
L
l
l
a
r
e
v
O
d
a
e
r
h
T
f
o
8
/
3
2
/
1
6
1
/
9
4
/
3
6
1
/
9
-
-
2
/
1
6
1
/
3
1
1
6
1
/
9
1
f
o
h
t
g
n
e
L
t
e
e
F
-
e
p
i
P
e
z
i
S
e
p
i
P
t
u
p
n
I
r
u
o
H
r
e
p
U
T
B
-
y
t
i
c
a
p
a
C
e
p
i
P
"
2
/
1
"
4
/
3
"
1
"
4
/
1
-
1
0
1
0
0
0
,
2
3
1
0
0
0
,
8
7
2
0
0
0
,
0
2
5
0
0
0
,
0
5
0
,
1
0
2
0
0
0
,
2
9
0
0
0
,
0
9
1
0
0
0
,
0
5
3
0
0
0
,
0
3
7
0
3
0
0
0
,
3
7
0
0
0
,
2
5
1
0
0
0
,
5
8
2
0
0
0
,
0
9
5
0
4
0
0
0
,
3
6
0
0
0
,
0
3
1
0
0
0
,
5
4
2
0
0
0
,
0
0
5
0
5
0
0
0
,
6
5
0
0
0
,
5
1
1
0
0
0
,
5
1
2
0
0
0
,
0
4
4
0
6
0
0
0
,
0
5
0
0
0
,
5
0
1
0
0
0
,
5
9
1
0
0
0
,
0
0
4
0
7
0
0
0
,
6
4
0
0
0
,
6
9
0
0
0
,
0
8
1
0
0
0
,
0
7
3
0
8
0
0
0
,
3
4
0
0
0
,
0
9
0
0
0
,
0
7
1
0
0
0
,
0
5
3
0
0
1
0
0
0
,
8
3
0
0
0
,
9
7
0
0
0
,
0
5
1
0
0
0
,
5
0
3
TABLE 6
GAS PIPE SIZES - NATURAL GAS
CHECKING THE GAS PIPING
Before turning gas under pressure into piping,
all openings from which gas can escape should be
closed. Immediately after turning on gas, the system
should be checked for leaks. This can be done by
watching the 1/2 cubic foot test dial and allowing 4
minutes to show any movement, and by soaping each
pipe connection and watching for bubbles. If a leak is
found, make the necessary repairs immediately and
repeat the above test. The furnace must be isolated
from the gas supply piping system by closing the
manual shutoff valve on the combination gas control
valve during pressure testing of the gas supply piping
system at pressures up to 1/2 PSIG. The furnace and its
individual shutoff valve must be disconnected from
supply piping and supply piping capped during any
pressure testing of supply piping system at test
pressures in excess of 1/2 PSIG.
Defective pipes or fittings should be replaced and not
repaired. Never use a flame or fire in any form to
locate gas leaks; use a soap solution.
After the piping and meter have been checked
completely, purge the system of air. DO NOT bleed air
inside the furnace. Be sure to check and relight all the
gas pilots on other appliances that may have been
extinguished because of interrupted gas supply.
MIS-897
FIGURE 13
PROPER PIPING PRACTICE
Summary of Contents for WG241
Page 12: ...Manual 2100 365 Page 9 FIGURE 2 MOUNTING INSTRUCTIONS FOR WG24 WG30 AND WG36 MIS 1681...
Page 13: ...Manual 2100 365 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472...
Page 16: ...Manual 2100 365 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474...
Page 22: ...Manual 2100 365 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1719...
Page 23: ...Manual 2100 365 Page 20 FIGURE 12 GAS PIPE CONNECTION MIS 1683...
Page 33: ...Manual 2100 365 Page 30 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Page 50: ...Manual 2100 365 Page 47 WG241 A 230 208 60 1...
Page 51: ...Manual 2100 365 Page 48 WG241 A 230 208 60 1...
Page 52: ...Manual 2100 365 Page 49 WG241 B 230 208 60 3...
Page 53: ...Manual 2100 365 Page 50 WG241 B 230 208 60 3...
Page 54: ...Manual 2100 365 Page 51 WG241 C 460 60 3...
Page 55: ...Manual 2100 365 Page 52 WG241 C 460 60 3...
Page 56: ...Manual 2100 365 Page 53 WG301 A WG361 A 230 208 60 1...
Page 57: ...Manual 2100 365 Page 54 WG301 A WG361 A 230 208 60 1...
Page 58: ...Manual 2100 365 Page 55 WG301 B WG361 B 230 208 60 3...
Page 59: ...Manual 2100 365 Page 56 WG301 B WG361 B 230 208 60 3...
Page 60: ...Manual 2100 365 Page 57 WG301 C WG361 C 460 60 3...
Page 61: ...Manual 2100 365 Page 58 WG301 C WG361 C 460 60 3...
Page 62: ...Manual 2100 365 Page 59 WG422 A 230 208 60 1...
Page 63: ...Manual 2100 365 Page 60 WG422 A 230 208 60 1...
Page 64: ...Manual 2100 365 Page 61 WG422 B 230 208 60 3...
Page 65: ...Manual 2100 365 Page 62 WG422 B 230 208 60 3...
Page 66: ...Manual 2100 365 Page 63 WG422 C 460 60 3...
Page 67: ...Manual 2100 365 Page 64 WG422 C 460 60 3...
Page 68: ...Manual 2100 365 Page 65 WG481 A WG601 A 230 208 60 1...
Page 69: ...Manual 2100 365 Page 66 WG481 A WG601 A 230 208 60 1...
Page 70: ...Manual 2100 365 Page 67 WG481 B WG601 B 230 208 60 3...
Page 71: ...Manual 2100 365 Page 68 WG481 B WG601 B 230 208 60 3...
Page 72: ...Manual 2100 365 Page 69 WG481 C WG601 C 460 60 3...
Page 73: ...Manual 2100 365 Page 70 WG481 C WG601 C 460 60 3...