background image

Manual 2100-365Q
Page

20 of 73

ELECTRICAL GROUNDING

When installed, the furnace must be electrically
grounded in accordance with local codes or in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or Canadian Electrical Code,
CSA22.1, latest edition.  Use a copper wire from green
ground wire on the furnace to a grounded connection in
the service panel or a properly driven and electrically
grounded ground rod.  See Tables 1 & 1A for proper
ground wire size.

FIELD INSTALLED EQUIPMENT

Wiring to be done in the field between the furnace and
devices not attached to the furnace, or between separate
devices which are field installed and located, shall
conform with the temperature limitation for Type T
wire {63 degrees F rise (36 degrees C)} when installed
in accordance with the manufacturer’s instructions.

INSTALLATION OF FLEXIBLE CONDUIT
THROUGH RETURN AIR OPENING

NOTE:  To allow proper clearance between the

control panel and any vent options, 90°
conduit fittings must be used on the back of
the control panel.

INSTALLING CONDUIT (See Figure 10.)

1. Remove conduit access panel if required to gain

access to area behind control panel.

2. Remove low voltage and high voltage knockouts

located in rear of control panel.

3. Run low voltage conduit through 7/8 bushing located

in conduit entrance plate and secure to low voltage
opening in rear of control panel.

4. Run high voltage conduit through 1-3/4 bushing

located in conduit entrance plate and secure to high
voltage opening in rear of control panel.

5. Replace conduit access panel if required to complete

installation.

6. Seal around conduit in conduit entrance plate.

         WARNING

Failure to provide a proper electrical ground
could result in electric shock or fire.

15. WIRING – MAIN POWER

Refer to unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.  All
models are suitable only for connection with copper
wire.  Each unit and/or wiring diagram will be marked -

Use Copper Conductors Only

”.  These instructions

must be

 adhered to.  Refer to the National Electrical

Code (NEC) for complete current carrying capacity
data on the various insulation grades of wiring material.
All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

        WARNING

For your personal safety, turn off electric
power at service entrance panel before
making any electrical connections.  Failure to
do so could result in electric shock or fire.

        WARNING

Failure to provide an electrical power supply
shut off means could result in electric shock
or fire.

Summary of Contents for WG242-A

Page 1: ...facturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2004 WARNING READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION THE INSTALLATION MUST COMPLY WIT...

Page 2: ...7 Thermostats 21 18 Gas Supply Piping 24 19 Manifold Pressure Adjustment 25 20 Checking Gas Input Rate 25 26 21 Standard Orifice Sizing High Altitude Derate 27 22 Conversion of Gas Input BTUH From Hig...

Page 3: ...f Operation Electronic Blower Control 36 Figure 18 Furnace Control Board Blower Control 37 Figure 19 Fan Blade 46 Figure 20 Low NOx Insert 46 TABLES Table 1 Specifications WG24 36 Models 7 Table 1A Sp...

Page 4: ...47 4044 COPYRIGHT SEPTEMBER 2003 BARD MANUFACTURING COMPANY INC BRYAN OHIO 43506 USA Manufactured under the following U S patent numbers 5 485 878 5 002 116 4 924 934 4 875 520 4 4825 936 These public...

Page 5: ...l a i c r e m m o C P 3 P V R C G W 5 P V R C G W g n i t a l u d o M y l l u F r e z i m o n o c E 1 E 3 M F I E G W 5 M F I E G W t l o V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E R 3 A...

Page 6: ...dure and any tags and or labels attached to the equipment All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors of Ame...

Page 7: ...8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 0 1 5 9 6 6 2 6 3 3 5 3 1 5 2 1 5 9 0 9 5 6 1 4 1 0 1 5 9 5 t n e r r u C n o i t c e l e S t i u c r i C h c n a r B 5 0 1 7 6 5 3 1 4 1 5 9 5 6 1 0 1 5...

Page 8: ...2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 9 1 1 2 5 4 1 5 3 1 8 5 1 2 1 2 3 1 5 2 1 2 6 0 3 7 2 5 9 1 7 1 9 t n e r r u C n o i t c e l e S t i u c r i C h c n a r B 1 2 5 1 6 7 2 2 3 1 4 6 0 3 5 9 1...

Page 9: ...N AIR EXHAUST COMBUSTION AIR INTAKE CONTROL LOW VOLTAGE ENTRANCES CIRCUIT BREAKER VENT OPTION MIS 2123 A UNIT A B C D E F G H I J K L M N O W G 24 W G 30 W G 3 6 7 88 27 88 13 88 24 25 40 25 63 81 63...

Page 10: ...nd in the absence of specific recommendations from the local authority having jurisdiction equipment ratings shall be reduced as specified in Section 21 5 TRANSPORTATION DAMAGE All units are packed se...

Page 11: ...ible wall use a minimum of Figure 1 A dimension plus 2 inches and B dimension plus 2 inches See Figures 4 and 5 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location 4...

Page 12: ...PTIONAL 12 FLANGE SCREWS UNIT SUPPORT 1 MIN NECCESSARY NO CLEARANCE SUPPLY AIR DUCT RETURN AIR DUCT CONTROL PANEL VESTIBULE DOOR WALL STRUCTURE OUTSIDE 1 CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT...

Page 13: ...Manual 2100 365Q Page 13 of 73 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...

Page 14: ...of one 1 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the one 1 inch m...

Page 15: ...Manual 2100 365Q Page 15 of 73 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...

Page 16: ...Manual 2100 365Q Page 16 of 73 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 17: ...ed air from the condenser to recirculate to the condenser inlet TABLE 2 MINIMUM INSTALLATION CLEARANCES s l a i r e t a m e l b i t s u b m o c m o r f t c u D t e l t u O t e e f 3 t s r i f h c n i...

Page 18: ...ang The kit includes a stainless steel transition drain tee silicone sealant and drain tubing If unit is installed with vertical vent kit annually inspect the vent system and drain Replace any portion...

Page 19: ...nce spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle 6 After it has been determined that each appliance connected to the venting sy...

Page 20: ...r electrical ground could result in electric shock or fire 15 WIRING MAIN POWER Refer to unit rating plate for wire sizing information and maximum fuse or HACR type circuit breaker size Each outdoor u...

Page 21: ...All models are equipped with single primary voltage transformers and no rewiring is required TABLE 3 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i...

Page 22: ...Manual 2100 365Q Page 22 of 73 FIGURE 11 LOW VOLTAGE WIRING...

Page 23: ...Manual 2100 365Q Page 23 of 73 FIGURE 12 GAS PIPE CONNECTION...

Page 24: ...0 0 0 0 5 0 5 0 0 0 6 5 0 0 0 5 1 1 0 0 0 5 1 2 0 0 0 0 4 4 0 6 0 0 0 0 5 0 0 0 5 0 1 0 0 0 5 9 1 0 0 0 0 0 4 0 7 0 0 0 6 4 0 0 0 6 9 0 0 0 0 8 1 0 0 0 0 7 3 0 8 0 0 0 3 4 0 0 0 0 9 0 0 0 0 7 1 0 0 0...

Page 25: ...kits may be purchased from your local distributor 5 Slowly open equipment shut off valve in gas supply line just ahead of furnace Start furnace following Operating Instructions on front door 6 Slowly...

Page 26: ...the furnace gas input PROPANE LP GAS INPUT RATE 1 Make sure you have proper main burner orifices 2 Gas supply pressure must be between 11 and 13 inches W C for propane LP gas 3 Start furnace followin...

Page 27: ...5 7 0 6 0 0 5 7 6 6 0 8 8 5 0 4 3 5 6 2 6 8 6 5 0 8 1 3 6 8 1 9 4 5 0 2 0 1 6 0 6 4 3 5 0 0 4 9 5 8 8 4 2 5 0 2 3 8 5 3 7 2 1 5 0 7 9 6 5 4 4 5 0 5 0 6 1 6 5 2 7 5 9 4 0 8 0 5 5 5 6 9 8 4 5 0 4 4 5 4...

Page 28: ...F 0 0 0 0 1 o t 1 0 0 8 h c t i w S e r u s s e r P s e r i u q e R e g n a h C e c i f i r O d n a e g n a h C t n e t n o C U T B n o d e s a B U T B 0 5 2 0 2 r e n r u B r e P 9 4 7 0 0 7 0 6 2 0...

Page 29: ...r e d 0 1 l a n o i t p o l a n o i t p O d l e i F 0 1 d e t r e v n o C e t a r e D t a e H s a G e u l a V t F u C U T B o N t e e F 0 0 0 6 o t p U t p e c x E s e g n a h C t n e t n o C U T B r...

Page 30: ...oximately 2 feet from furnace Locate thermometer tip in center of plenum to insure proper temperature measurement 6 Place second thermometer in return air duct approximately 2 feet from furnace Locate...

Page 31: ...ontactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on make time has expired If the high pr...

Page 32: ...e DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 minute 30 seconds DOB 123 second DOM 1 0 minute 60 seconds DOB 126 second DOM 2 0...

Page 33: ...Manual 2100 365Q Page 33 of 73 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...

Page 34: ...ht on small mirror or an extension handle Remove the screws securing the inducer and collector box Now inspect the upper tubes of the heat exchanger Check the exterior of the heat exchanger and the in...

Page 35: ...sure the supply and return air flange sleeves or duct work are securely fastened to unit and physically sound d Supply and return grilles must be open and free from obstructions e Inspect to make sur...

Page 36: ...cle on and off until the condensing pressure remains above 180 PSIG LAC energizes the fan motor at 280 PSIG de energizes at 180 PSIG FIGURE 17 SEQUENCE OF OPERATION ELECTRONIC BLOWER CONTROL N O I T C...

Page 37: ...f it is desirable to have both HEAT COOL blower motor speed at the same speed install a jumper wire between HEAT and COOL terminals of the integrated furnace control board and place both unused motor...

Page 38: ...0 7 0 2 1 1 0 2 1 1 0 4 9 4 0 0 9 7 0 3 0 1 0 3 0 1 0 6 8 5 0 0 1 9 0 1 7 0 5 9 6 0 0 0 8 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C t e W...

Page 39: ...3 0 1 0 9 1 1 0 3 0 1 0 6 8 5 0 0 5 0 1 0 1 9 0 9 0 1 0 5 9 0 9 0 1 0 5 9 6 0 0 4 9 0 8 9 0 8 9 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C...

Page 40: ...1 0 3 0 1 0 9 1 1 0 3 0 1 0 6 8 5 0 0 5 0 1 0 9 0 1 0 5 9 0 9 0 1 0 5 9 6 0 0 4 9 0 8 9 0 8 9 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C...

Page 41: ...3 1 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w o L h g...

Page 42: ...0 4 3 1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e...

Page 43: ...3 1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w...

Page 44: ...c e l e s e h t r o f e t a r e p o l l i w r e w o l b r i a t r o f m o c e h t e t a r e p o o t e u n i t n o c l l i w r e w o l b r i a t r o f m o c e h t n o i t a r e p o S T I N U Y T E F A...

Page 45: ...8 6 2 3 2 8 6 4 3 3 8 6 6 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 8 2 2 9 7 5 4 2 1 8 2 6 2 2 8 9 7 2 4 8 8 9 2 5 8 6 1 3 7 8 5 3 3 8 8 5 5 3 9 8 5 7 3 B D g e d 5 8 B W g e d...

Page 46: ...9 FAN BLADE 36 LOW NOX BURNER ASSEMBLY N SUFFIX MODELS ONLY U S INSTALLATIONS ONLY NATURAL GAS MODELS ONLY Model numbers designated with an N are designed for low NOx emissions which comply with all C...

Page 47: ...7 5 C 3 0 3 G W 3 4 3 5 8 0 4 8 5 A 4 4 3 5 8 0 4 9 5 A 2 6 3 G W A 8 3 1 5 8 0 4 0 6 A 5 3 1 5 8 0 4 9 4 B 2 6 3 G W A 8 3 2 5 8 0 4 1 6 A 5 3 2 5 8 0 4 1 5 C 3 6 3 G W 5 4 3 5 8 0 4 2 6 A 6 4 3 5 8...

Page 48: ...Manual 2100 365Q Page 48 of 73 WG242 A 230 208 60 1...

Page 49: ...Manual 2100 365Q Page 49 of 73 WG242 A WG362 A 230 208 60 1...

Page 50: ...Manual 2100 365Q Page 50 of 73 WG242 B 230 208 60 3...

Page 51: ...Manual 2100 365Q Page 51 of 73 WG242 B WG362 B 230 208 60 3...

Page 52: ...Manual 2100 365Q Page 52 of 73 WG243 C 460 60 3...

Page 53: ...Manual 2100 365Q Page 53 of 73 WG243 C 460 60 3...

Page 54: ...Manual 2100 365Q Page 54 of 73 WG302 A 230 208 60 1...

Page 55: ...Manual 2100 365Q Page 55 of 73 WG302 A WG482 A WG602 A 230 208 60 1...

Page 56: ...Manual 2100 365Q Page 56 of 73 WG302 B 230 208 60 3...

Page 57: ...Manual 2100 365Q Page 57 of 73 WG302 B WG482 B WG602 B 230 208 60 3...

Page 58: ...Manual 2100 365Q Page 58 of 73 WG303 C 460 60 3...

Page 59: ...Manual 2100 365Q Page 59 of 73 WG303 C 460 60 3...

Page 60: ...Manual 2100 365Q Page 60 of 73 WG362 A 230 208 60 1...

Page 61: ...Manual 2100 365Q Page 61 of 73 WG362 B 230 208 60 3...

Page 62: ...Manual 2100 365Q Page 62 of 73 WG363 C 460 60 3...

Page 63: ...Manual 2100 365Q Page 63 of 73 WG363 C 460 60 3...

Page 64: ...Manual 2100 365Q Page 64 of 73 WG423 A 230 208 60 1...

Page 65: ...Manual 2100 365Q Page 65 of 73 WG423 A 230 208 60 1...

Page 66: ...Manual 2100 365Q Page 66 of 73 WG423 B 230 208 60 3...

Page 67: ...Manual 2100 365Q Page 67 of 73 WG423 B 230 208 60 3...

Page 68: ...Manual 2100 365Q Page 68 of 73 WG424 C 460 60 3...

Page 69: ...Manual 2100 365Q Page 69 of 73 WG424 C 460 60 3...

Page 70: ...Manual 2100 365Q Page 70 of 73 WG482 A WG602 A 230 208 60 1...

Page 71: ...Manual 2100 365Q Page 71 of 73 WG482 B WG602 B 230 208 60 3...

Page 72: ...Manual 2100 365Q Page 72 of 73 WG483 C WG603 C 460 60 3...

Page 73: ...Manual 2100 365Q Page 73 of 73 WG483C WG603 C 460 60 3...

Reviews: