20
6.4-4 Connection of the unit to
the BMS control system
The ventilation unit control is normally
equipped with the RS-485 interface.
For connection use
a
standard communication
cable.
Connect the cable to the assigned
MODBUS connectors on the control board.
Connect the other end to the main control unit.
For the protocols details (ModBUS) contact
Barkell.
IMPORTANT NOTICE!
It is possible to connect the unit to the BMS control
system and the unit controller at the same time.
BMS communication is only available through the
RS-485 Modbus interface. Other communication
protocols will require a gateway translator.
For additional information about the MODBUS co
-
nnection please consult the THERM-X HRFL Mod
-
bus Protocol manual.
6.5 CONDENSATE DRAIN
CONNECTION
Condensate drain from the unit (either from the
re
cuperator, the cooling coil (if provided) or both
must
be connected to the discharge pipeline.
If the unit has 2 drain connections an additional
trap
or
pump
is
required.
Ensure the unit is level or angled slightly towards
the
condensate tray outlet to facilitate correct
conden-
sate removal from the unit.
YOU WILL NEED
• 1 siphon
• PVC discharge pipework
• seal to the discharge pipework
Siphon with a ball
The tube connection on the drain is connected
to
the side discharge on the ventilation unit.
Ensure ALL connections are TRAPPED.
6. INSTALLATION
– Make sure that the unit is inclined by 3° so that
the condensate drain is ensured.
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
EN
RU
CZ
1.
A
(5-6)
LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open)
LF1 ЗАСЛОНКА ВПУСК (выход L-открыт), LF2 - ЗАСЛОНКА ВЫПУСК (выход L-открыт)
LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2.
A
(7-8)
RUN CONTACT (output -NO/NC settable)
RUN контакт (выход - NO/NC устанавливаемый)
RUN KONTACT (výstup -NO/NC nastavitelné)
3.
A
(9-10)
ERROR CONTACT (output NO)
ОШИБКА КОНТАКТА (выход NO)
ERROR KONTACT (výstup NO)
4.
A
(11-12)
PREHEATER WATER PUMP (11 - Lint, 12 - Lout)
ВОДЯНОЙ НАСОС ПРЕДВАРИТЕЛЬНОГО НАГРЕВА (11 - Lint,12 - Lout)
VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5.
A
(13-14)
BOOST (input NO)
BOOST (вход NO)
BOOST (vstup NO)
6.
A
(15-16)
FIRE (input NC)
FIRE -тревога (вход NC)
FIRE (vstup NC)
7.
A
(17-18)
EXTERNAL CONTROL ON/OFF (input NC)
ВНЕШНЕЕ УПРАВЛЕНИЕ ON/OFF (вход NC)
EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8.
A
(18-19)
AQS SENSOR 0-10V (input)
ДАТЧИК КАЧЕСТВА ВОЗДУХА 0-10В (вход)
ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9.
B
(1-2)
WATER PUMP (1 - Lint, 2 - Lout)
ВОДЯНОЙ НАСОС (1 - Lint, 2 - Lout)
VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10.
B
(3-4)
HEAT PUMP CONTROL settable (output - ON/OFF)
УПРАВЛЕНИЕ ТЕПЛОВОГО НАСОСА устанавливаемый (выход - ON/OFF)
ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11.
B
(5-6)
ADIABATIC MODULE (output - ON/OFF)
АДИАБАТИЧЕСКИЙ МОДУЛЬ (выход - ON/OFF)
ADIABATICKÝ MODUL (výstup - ON/OFF)
12.
B
(7-8)
COOL / HEAT settable (CO = NC/NO - DX = output settable)
ОХЛАЖДЕНИЕ /ОБОГРЕВ устанавливаемый (CO = NC/NO - DX = выход устанавливаемый)
CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13.
B
(9-10)
ADIABATIC MODULE ERROR (input NO)
АДИАБАТИЧЕСКИЙ МОДУЛЬ ERROR (вход NO)
ADIABATICKÝ MODUL ERROR (vstup NO)
14.
B
(11-12)
HEAT PUMP DEFROST settable (input NC/NO)
РАЗМОРАЖИВАНИЕ ТЕПЛОВОГО НАСОСА устанавливаемое (вход NC/NO)
ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15.
B
(13-14)
HEAT PUMP ERROR settable (input NC/NO)
ОШИБКА ТЕПЛОВОГО НАСОСА устанавливаемая (вход NC/NO)
CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16.
B
(15-16)
PIR (input NC)
ДАТЧИК ДВИЖЕНИЯ PIR (вход NC)
POHYBOVÉ ČIDLO PIR (vstup NC)
17.
B
(17-18)
CONDENSATE OVERFLOW (input NC)
ДАТЧИК ПЕРЕПОЛНЕНИЯ КОНДЕНСАТА (вход NC)
ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18.
B
(46-47)
EXTERNAL TEMPERATURE SENSOR (external postheater - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (внешний дополнительный нагрев - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19.
B
(44-45)
EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (адиабатический модуль / камера рециркуляции - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20.
B
(38-39)
EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ПОДОГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21
B
(36-37)
EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ДООГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22
B
(34-35)
RECIRCULATION CHAMBER (output 0-10V)
РЕЦИРКИЛИРОВАННАЯ КАМЕРА (выход 0-10В)
RECIRKULAČNÍ KOMORA (výstup 0-10V)
A
B
MODBUS connection