background image

CASE CONNECTIONS

REFRIGERATION

Refrigeration connections will be made through the refrigera-
tion stub up location on the customer left side of the case.   
Refrigeration lines may be headed together for all cases in a 
line-up, if necessary, by lines through the access holes with a 
high grade silicon to prevent recirculation.  All lines must be 
correctly sized. 

See diagram on page 9 for access locations.

If it becomes necessary to penetrate the case bottom for any 
reason, make certain it is sealed afterward with canned-foam 
sealant and white RTV.

ELECTRICAL

Electrical hookups are made through the power supply box 
that can be accessed by removing the back panel.

For case-to-case wiring, run conduit between the power supply 
boxes or run wiring through the raceway.  When connecting to 
the po

wer supply on the case, fi eld wiring should exit box from 

the side furthest away from case wiring to allow more room in-
side for wiring connections.  Always check the data tag located 
on left end exterior panel or top interior of the case.  The case 
must be grounded.  

For more detailed electrical wiring infor-

mation, see Appendices A1-A2.

     

C A U T I O N

Be certain that all plumbing connections are 
compliant with local codes.

 

     

C A U T I O N

Be certain that all electrical connections are 
compliant with local codes.

 

     

C A U T I O N

Be sure to remove all styrafoam shipping blocks 
from piping and refrigerant lines.  Failure to do 
so may result in case damage.

 

Fig. 4  "P" trap / drain outlet

PLUMBING

The drain outlet or “P” trap (Fig. 4) is shipped loose with the 
case and made from a 1 1/2” PVC pipe. Care should be given 
to ensure that all connections are water-tight and sealed with 
the appropriate PVC or ABS cement.

Drain lines can be run left or right of the tee with the proper 
pitch to satisfy local drainage requirements.  When connecting 
the PVC to the e

xisting fl oor drains be sure to provide as much 

downhill slope as possible and avoid long runs of drain lines.  

Do not install condensate drains in contact with non-insulated 
suction lines in order to prevent condensate from freezing.  
Install the 1 1/2" PVC trap, which is provided with the case.  All 
drains must be trapped.

Before operating the case, be certain to remove the styrafoam 
shipping block that protects the plumbing lines during ship-
ping.

     

C A U T I O N

If any brazing is necessary, place wet rags 
around the area to avoid tank damage.

 

 

   

C A U T I O N

Be certain that all piping connections are com-
pliant with local codes.

 

     

C A U T I O N

If the shelves are removed from the case or other-
wise not utilized, the shelf setpoint (SAA) must be 
raised  to 90 

o

F  to prevent the pump from running 

when only the shelves are calling for refrigeration.  
Failure to do so could result in early pump failure.

 

8

Summary of Contents for AGB

Page 1: ...ase Cleaning 14 15 Parts Ordering 16 Appendices Table of Contents To ensure proper functionality and optimum performance it is STRONGLY recommended that Hillphoenix specialty cases be installed servic...

Page 2: ...ii...

Page 3: ...ith shelf lighting systems for direct or indirect exposure to water or other liquids The use of a misting system or water hose on a display case with a shelf lighting system resulting in the direct or...

Page 4: ...installation and operations handbooks accompanied by an alert symbol paired with the word DANGER WARNING or CAUTION All warning messages will inform you of the potential hazard how to reduce the risk...

Page 5: ...parts list_09 12 energy data and parts list_01 13 endviews_03 13 text update and air ow diagram_06 13 energy data_07 13 energy data_02 14 endviews and energy data_09 14 support diagram and parts page...

Page 6: ...Watts Amps Watts Amps Watts Amps Watts AGB 4 6 8 Model Lights per Row Light Length ft Fluorescent Lighting Per Light Row Clearvoyant LED Lighting Per Light Row Standard Power Cornice or Shelf High Pow...

Page 7: ...ghted shelves Add the following for lighted shelves 4 Fluorescent 80 BTUH 3 Fluorescent 60 BTUH 4 Shelf LED 36 BTUH 4 Canopy LED 72 BTUH 3 Shelf LED 27 BTUH 3 Hi Output LED 54 BTUH 6 EPR valve is fact...

Page 8: ...cm 21 13 16 in 55 4 cm 49 13 16 in 126 5 cm 93 1 2 in 237 5 cm 93 1 2 in 237 5 cm 49 1 4 in 125 1 cm 49 1 4 in 125 1 cm REFLECTIVE REAR LOAD DOORS REFLECTIVE REAR LOAD DOORS 30 PROFILE 36 PROFILE 48...

Page 9: ...e it is delivered to the consumer Our liability ceases at the time of shipment RECEIVING CASES Examine fixtures carefully and in the event of shipping dam age and or shortages please contact the Servi...

Page 10: ...cross support and lower the horizontal support on to the shim packs Repeat on the other end of the case LOCATION This refrigerated display case has been designed for displaying and storing perishable...

Page 11: ...umper for nal t and n ish Be certain to use an appropriate cutting tool tubing or PVC cutter to ensure a smooth cut 7 Install case shelves and reconnect lights Be aware that differing shelf con gurati...

Page 12: ...ns are compliant with local codes C A U T I O N Be sure to remove all styrafoam shipping blocks from piping and refrigerant lines Failure to do so may result in case damage Fig 4 P trap drain outlet P...

Page 13: ...43 8 cm 8 case 18 in 45 7 cm 14 in 35 6 cm 28 in 71 1 cm 30 34 in 86 4 cm 36 30 in 76 2 cm 36 in 91 4 cm 26 in 66 0 cm 30 32 in 81 3 cm 36 TOEKICK 15 x 15 MECHANICAL ACCESS FOR ELECT REFRIG AND DRAIN...

Page 14: ...G E R SHOCK HAZARD Always disconnect power to case when cleaning servicing or con guring components of the light ing system Failure to do so may result in serious injury or death REPLACING T 8 LIGHTS...

Page 15: ...remove Re installing shelf luminaires 1 Place hook into shelf roll form at shelf front and rotate rear of luminaire toward the shelf 2 Depress the rear clip so that luminaire can nish rotation and un...

Page 16: ...ines see pg 8 After powering up the case be certain that all of the steps listed below have been completed to ensure proper case functionality safety and compliance with warranty terms 1 Check all lig...

Page 17: ...a case 1 Store Conditions Hillphoenix cases are designed to oper ate in an air conditioned store that maintains a 75 F 24 C store temperature and 55 max relative humidity ASHRAE conditions Case opera...

Page 18: ...he luminaires down with a soft damp cloth Avoid using harsh or abrasive cleaners as they may dam age the lights Be certain that the luminaires are complete ly dry before re energizing Clean from top t...

Page 19: ...product only extra strength or specialty products may not be suitable Glass Plus standard product only extra strength or specialty products may not be suitable Exceed Multi Surface Glass Cleaner from...

Page 20: ...case for which the part is intended Length of the part if applicable Color of part if painted or color of polymer part Whether part is for left or right hand application Quantity Data tag is located o...

Page 21: ...A1 A2 Wiring Information B1 B4 Dixell Operating Instructions C1 Sporlan Pressure Temperature Chart D1 Parts List APPENDIX 17...

Page 22: ...A1 WIRING DIAGRAM...

Page 23: ...UE LIGHT BLACK LIGHT SWITCH WHITE FROM 2 2 BLACK BALLAST WHITE BALLAST BLACK LIGHT RED LIGHT BLACK FROM BLOCK 1 1 BLACK TO DIXELL 5 41 WHITE TO DIXELL 6 42 WHITE SOL JUNCTION BOX 26 27 78 BLACK TO CHI...

Page 24: ...int 3 1 DEFROST Defrost is performed through a simple stop of the compressor Parameter IdF controls the interval between defrost cycles while its length is controlled by parameter MdF To disable the d...

Page 25: ...ow and above the humidity set point SET_RH The dehumidifying action is enabled when the humidity increases and reaches the SET_RH dbH value It is stopped when it comes back to the SET_RH The humidifyi...

Page 26: ...ring this time and then for the delay dot and doH after closing the door the temperature and humidity alarms are disabled 7 2 GENERIC ALARM I1F EAL As soon as the digital input is activated the unit w...

Page 27: ...ative humidity 20y85 no condensing Measuring and regulation range NTC probe 40 110 C 58 230 F Resolution 0 1 C or 1 C or 1 F selectable Accuracy ambient temp 25 C 0 5 C 1 digit 13 WIRING CONNECTIONS 1...

Page 28: ...29 4 381 8 17 8 3 16 4 51 5 54 3 30 4 388 0 18 7 8 17 0 52 7 55 6 31 4 394 3 19 7 2 17 7 54 0 56 9 32 4 400 7 20 6 7 18 4 55 3 58 3 33 5 407 2 21 6 1 19 1 56 6 59 6 34 6 413 8 22 5 6 19 9 58 0 61 0 3...

Page 29: ...S Wire Riser F Front Toekick G Outside Front H End Toekick I Dry or Refrigerated Lower Storage J End Panel K Fixed End Glass L Shelf Standard M Outside Back N Rear Load Doors O Light Guard P Upper Int...

Page 30: ...rned within two weeks after startup 5 If the defective part is not returned to the Manufacturer 6 To service maintenance or wear and tear parts such as lights starters and ballasts MODIFICATIONS TO GE...

Page 31: ...er directly on fan motors or any electrical connections All lighting receptacles must be dried off prior to insertion and re energizing the lighting circuit Please refer to the Use and Maintenance sec...

Reviews: