CASE CONNECTIONS
REFRIGERATION
Refrigeration connections will be made through the refrigera-
tion stub up location on the customer left side of the case.
Refrigeration lines may be headed together for all cases in a
line-up, if necessary, by lines through the access holes with a
high grade silicon to prevent recirculation. All lines must be
correctly sized.
See diagram on page 9 for access locations.
If it becomes necessary to penetrate the case bottom for any
reason, make certain it is sealed afterward with canned-foam
sealant and white RTV.
ELECTRICAL
Electrical hookups are made through the power supply box
that can be accessed by removing the back panel.
For case-to-case wiring, run conduit between the power supply
boxes or run wiring through the raceway. When connecting to
the po
wer supply on the case, fi eld wiring should exit box from
the side furthest away from case wiring to allow more room in-
side for wiring connections. Always check the data tag located
on left end exterior panel or top interior of the case. The case
must be grounded.
For more detailed electrical wiring infor-
mation, see Appendices A1-A2.
C A U T I O N
Be certain that all plumbing connections are
compliant with local codes.
▲
C A U T I O N
Be certain that all electrical connections are
compliant with local codes.
▲
C A U T I O N
Be sure to remove all styrafoam shipping blocks
from piping and refrigerant lines. Failure to do
so may result in case damage.
▲
Fig. 4 "P" trap / drain outlet
PLUMBING
The drain outlet or “P” trap (Fig. 4) is shipped loose with the
case and made from a 1 1/2” PVC pipe. Care should be given
to ensure that all connections are water-tight and sealed with
the appropriate PVC or ABS cement.
Drain lines can be run left or right of the tee with the proper
pitch to satisfy local drainage requirements. When connecting
the PVC to the e
xisting fl oor drains be sure to provide as much
downhill slope as possible and avoid long runs of drain lines.
Do not install condensate drains in contact with non-insulated
suction lines in order to prevent condensate from freezing.
Install the 1 1/2" PVC trap, which is provided with the case. All
drains must be trapped.
Before operating the case, be certain to remove the styrafoam
shipping block that protects the plumbing lines during ship-
ping.
C A U T I O N
If any brazing is necessary, place wet rags
around the area to avoid tank damage.
▲
C A U T I O N
Be certain that all piping connections are com-
pliant with local codes.
▲
C A U T I O N
If the shelves are removed from the case or other-
wise not utilized, the shelf setpoint (SAA) must be
raised to 90
o
F to prevent the pump from running
when only the shelves are calling for refrigeration.
Failure to do so could result in early pump failure.
▲
8
Summary of Contents for AGB
Page 2: ...ii...
Page 22: ...A1 WIRING DIAGRAM...