7
C-4) Electrical Connections:
C-4.1) Power & Sensor Cords:
The cord assembly mounted to the pump must not be modifi ed
in any way except for shortening to a specifi c application.
Any splice between the pump and the control panel must be
made in accordance with all applicable electric codes. It is
recommended that a junction box, if used, be mounted outside
the sump or be of at least NEMA 4 (EEMAC-4) construction if
located within the wet well.
DO NOT USE THE POWER OR
SENSOR CORDS TO LIFT PUMP.
NOTE: The White Wire Is Not A Neutral Or Ground Lead.
The Black, White And Red Leads Are Power Carrying
Conductors. The Green Lead Is For Connection To
Ground.
C-4.2) Overload Protection :
C-4.2-1) Three Phase -
The normally closed (N/C) thermal
sensor is embedded in the motor windings and will detect
excessive heat in the event an overload condition occurs. The
thermal sensor will trip when the windings become too hot and
will automatically reset itself when the pump motor cools to a
safe temperature. It is recommended that the thermal sensor
be connected in series to an alarm device to alert the operator
of an overload condition, and/or the motor starter coil to stop
the pump. In the event of an overload, the source of this
condition should be determined and rectifi ed immediately.
DO
NOT LET THE PUMP CYCLE OR RUN IF AN OVERLOAD
CONDITION OCCURS !
C-4.2-2) Single Phase -
The type of in-winding overload
protector used is referred to as an inherent overheating
protector and operates on the combined effect of temperature
and current. This means that the overload protector will trip out
and shut the pump off if the windings become too hot, or the
load current passing through them becomes too high. It will
then automatically reset and start the pump up after the motor
cools to a safe temperature. In the event of an overload, the
source of this condition should be determined and rectifi ed
immediately.
DO NOT LET THE PUMP CYCLE OR RUN IF
AN OVERLOAD CONDITION OCCURS !
C-4.3) Moisture Sensors:
A normally open (N/O) detector is installed in the pump
seal chamber which will detect any moisture present. It is
recommended that this detector be connected in series to an
alarm device or the motor starter coil to alert the operator that
a moisture detect has occurred. In the event of a moisture
detect, check the individual moisture sensor probe leads for
continuity, ( ∞ resistance = no moisture ) and the junction
box/control box for moisture content. The above situations
may induce a false signal in the moisture detecting circuit. If
none of the above test prove conclusive, the pump(s) should
be pulled and the source of the failure identifi ed and repaired.
IF A MOISTURE DETECT HAS OCCURRED SCHEDULE
MAINTENANCE AS SOON AS POSSIBLE.
If current through the temperature sensor exceeds the values
listed, an intermediate control circuit relay must be used to
reduce the current or the sensor will not work properly.
TEMPERATURE SENSOR ELECTRICAL RATINGS
Volts
Continuous
Amperes
Inrush
Amperes
220-240
1.50
15.0
440-480
0.75
7.5
575-600
0.60
6.0
C-4.4) Wire Size:
Consult a qualifi ed electrician for proper wire size if additional
power cable is required. See table for electrical information.
SECTION: D START-UP OPERATION
D-1) Check Voltage and Phase:
Before operating pump, compare the voltage and phase
information stamped on the pump identifi cation plate to the
available power.
D-2) Check Pump Rotation:
Before putting pump into service for the fi rst time, the motor
rotation must be checked. Improper motor rotation can result
in poor pump performance and can damage the motor and/or
pump. To check the rotation, suspend the pump freely, mo-
mentarily apply power and observe the “kickback”. “Kickback”
should always be in a counter-clockwise direction as viewed
from the top of the pump motor housing.
D-2.1) Incorrect Rotation for Three-Phase Pumps:
In the event that the rotation is incorrect for a three-phase
installation, interchange any two power cable leads at the
control box.
DO NOT
change leads in the cable housing in
the motor. Recheck the “kickback” rotation again by momen-
tarily applying power.
D-2.2) Incorrect Rotation for Single-Phase Pumps:
In the unlikely event that the rotation is incorrect for a single
phase pump, contact a CP&S Service Center.
D-3) Identifi cation Plate:
Record the numbers from the pump identifi cation plate for
future reference.
D-3.1) Insulation Test:
Before the pump is put into service, an insulation (megger)
test should be performed on the motor. The resistance values
(ohms) as well as the voltage (volts) and current (amps)
should be recorded.
D-3.2) Pump-Down Test
:
After the pump has been properly wired and lowered into the
basin, sump or lift station, it is advisable to check the system
by fi lling with liquid and allowing the pump to operate through
its pumping cycle. The time needed to empty the system, or
pump-down time along with the volume of water, should be
recorded.
Summary of Contents for 4SE-L series
Page 14: ...14 FIGURE 11...