Operational Instruction 

(Original)

 

 

Distribution box 

Type 07-56..-…./…. 

 

 

BARTEC 
Varnost d.o.o. 

Cesta 9.avgusta 59 
1410 Zagorje ob Savi 
Slovenia 

Tel.:  +386 59 221 471 
Fax:  +386 59 221 470 

info@bartecvarnost.si 
www.bartecvarnost.si 

Reservation

 

Technical data subject to change without notice. Changes, errors and 
misprints may not be used as a basis for any claim for damages. 

EN 2/3

 

 

 

V

S

 –

 1

01

 3

51

 (

is

su

N

I /

 2

.1

1.

20

16

Safety instructions 

The  distribution  box  may  be  used  within  the 
specified  temperature  class  and  the  tempera-
ture range indicated for it (see type label). The 
distribution box is not suitable for use in Zones 
0/20. 
As  for  distribution  boxes  used  in  flammable 
dust,  the  ignition  temperature  of  the  dust/air 
mixture  and  the  glowing  temperature  of  the 
dust  concerned  must  be  greater  than  the 
maximum  surface  temperature  of  the  distribu-
tion box taking into account of the given safety 
factor specified in EN 60079-0. 
The distribution box may  be operated only if  it 
is  clean  and  not  damaged  in  any  way.  Dust 
deposits > 5 mm (> 0.2 in) must be removed. 
Utilization in areas other than those specified or 
the modification of the product by anyone other 
than the manufacturer is not permitted and will 
exempt  BARTEC  Varnost  from  liability  for 
defects and any further liability. 
The  generally  applicable  statutory  rules  and 
other  binding  directives  relating  to  workplace 
safety,  accident  prevention  and  environmental 
protection must be observed. 
Observe  the  applicable  laws  and  directives 
when commissioning or restarting operation. 
Always  follow  the  safety  instructions  on  the 
operating equipment. 
 

Marking 

Particularly  important  points  in  these  instruc-
tions are marked with a symbol: 
 

 

DANGER  indicates  a  hazardous  situation
which,  if  not  avoided,  will  result  in  death  or 
serious injury. 

 

WARNING  indicates  a  hazardous  situation 
which,  if  not  avoided,  could  result  in  death  or 
serious injury. 

 

CAUTION  indicates  a  hazardous  situation
which,  if  not  avoided,  could  result  in  minor  or 
moderate injury.  

 

NOTICE is used to address practices not 
related to personal injury. 
 

 

Note 

Important  instructions  and  information  on 
effective,  economical  and  environmentally 
compatible handling.

 

 
 

 

Standards conformed to 

2014/34/EU 
as well as 
EN 60079-0:2012/IEC 60079-0:20011 
EN 60079-7:2007/IEC 60079-7:2006-7 
EN 60079-11:2012/IEC 60079-11:2011 
EN 60079-31:2009/IEC 60079-31:2008 
as well as 
EN 62208:2011/IEC 62208:20011 
EN 60445:2010/IEC 60445:2010 
EN 60529:1991 + A1:2000 
 

Transport, storage 

 

Risk of injury due to heavy loads. 

 

Use  an  appropriate  carrying  aid  or  an 
appropriate means of transport (e.g. a fork-
lift) with an adequate load-carrying ability. 

 

Ensure  that  the  lifted  load  will  not  tip  over 
or slip off. 

 

Damage through incorrect transport or 
incorrect storage. 

 

Transport  the  distribution  box  in  original 
packaging,  handle  with  care,  and  do  not 
drop. 

 

Store  the  distribution  box  dry  in  original 
packaging. 

 

Assembly, installation, and 
commissioning 

 

Risk of serious injury due to incorrect 
proceedings. 

 

Only 

qualified 

personnel 

who 

are 

authorized and trained to assemble electri-
cal  components  in  hazardous  (potentially 
explosive)  areas  may  do  any  of  the  as-
sembly,  disassembly,  installation  and 
commissioning work. 

 

For  assembly  and  operation  of  explosion 
protected electrical equipment, relevant in-
stallation  and  operating  regulations  are  to 
adhere (e.g. Betr.SichV, IEC/EN 60079-14 
and series DIN VDE 0100). 

 

The data on the label and the EEC design 
test data are to be observed. Further tech-
nical information are provided in the Bartec 
catalog and on the product itself.  

 

User  may  not  drill  holes  in  the  distribution 
boxes and add terminals 

 

Do  not  open  the  distribution  box  when 
energized. 

 

 

Assembly / disassembly 

 

Death or serious injury because of a miss-
ing protective earth connection. 

 

Metallic  distribution  boxes  in  hazardous 
areas require equipotential bonding with at 
least 4 mm².  

 

Protective  earth  connections  have  to  be 
protected against self-loosening. 

 

Risk of serious injury due to incorrect pro-
ceedings. 

 

The  assembly  with  connecting  and/or  rail-
mounted  terminals  must  be  implemented 
under the consideration of the EEC design 
inspection certificate.  

 
Check when assembling: 

 

Use suitable tools. 

 

Pay  attention  to  the  type  of  mounting 
required 

(for 

fitting 

into 

enclo-

sure/attachment with junction box). 

 

For distribution boxes placed in outdoors, 
steps  must  be  taken  to  ensure  smooth 
operation,  for  example  rain  protected 
roofs,  and  if  necessary,  sufficient  enclo-
sure protection.  

 

 

Note 

Metallic  distribution  boxes  for  intrinsically  safe 
facilities  do  not  have  to  be  attached  to  an 
equipotential  bonding  system,  except  if  it  is 
required by equipment documentation.  

Installation 

 

Risk of serious injury due to incorrect pro-
ceedings. 

 

Extensions or modifications to the distribu-
tion  box  are  only  permissible  if  the  manu-
facturer’s approval is obtained first. 

 

The IEC/EN60079-14 must be observed. 

 
Installations  for  the  highly  combustible  range 
must  exhibit  an  EEC  design  inspection  certifi-
cate.  Installation  of  these  components  must 
take  place  in  such  way,  so  that  at  least  the 
enclosure remains IP54. 
Connection of cables and conductors to equip-
ment  in  hazardous  areas  require  Ex-certified 
entries,  which are suitable for  respective cable 
and  conductor  types.  They  must  possess  the 
protection type e” and contain a suitable sealing 
gasket. 
Unused  holes  for  cable  entries  must  been 
sealed  with  Ex-certified  plugs.  Connection  of 
cables  and  conductors  of  zone  21  and  22 
equipment  require  at  least  the  protection  class 
IP66.  
 
 

 