BARTEC
www.bartec.de
11-85M1-7D0002-03/2017-BAR
TEC-320201
M
Reservation
Technical data subject to change without notice. No claims for damages arising from alterations, errors or misprints shall be allowed.
EN 4/4
Item Installed
cable
length
in metres
Measured
insulation
resistance
in MΩ
between conductors
1 and 3
before installation
Measured
insulation
resistance
in MΩ
between conductors
1 and 3
after installation
*
Measured
insulation
resistance
in MΩ
between
conductor 1 to ground
conductor 3 to ground**
Volume
resistance
in Ω
between
conductors 1 and 2
conductors 3 and 4*
Calculated
volume
resistance
in Ω/m
**
Date of test/
test engineer
conductor
1
conductor
3
conductor
1 and 2
conductor
3 and 4
1
2
3
4
Note
The sensor cable must be checked during assembly also. When checking, disconnect the sensor cable from the monitoring electronics.
Test tolerance for the measurements
Volume resistance in Ω: min: 5.7 Ω/m, max: 6.3 Ω/m
Insulation resistance in MΩ: not less than 10 MΩ per entire measuring circuit (at a test voltage of 500 V)
Conductor 1 = contact 1 = wire white with perforation
Conductor 2 = contact 2 = wire white insulated
Conductor 3 = contact 3 = wire red with perforation
Conductor 4 = contact 4 = wire red insulated
All warranty claims are subject to the submission of a correctly and completely fi lled-in acceptance report. Date and signature are also required.
Customer
Commission number
Project
Building
Test Report on SCR sensor cable
Type 17-85M1-1761, assembled with plug and socket
* (measured with end plug), measurement section: sensor cable with incoming feed line
** (measured resistance of conductors 1 and 3 in Ω/installed cable length = calculated resistance in Ω/m)
Stamp/signature of installation company