Ex p control unit
Motor purge controller
Maintenance and repair
Rev. 0
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Page 81 of 96
10.4.2.2
Warning messages
Status
Code
Plain text
00000005
Bypass active
The bypass has been activated on the control unit.
00000006
Door contact / main switch open
The main switch or jumper HS_IN / HS_OUT is not closed.
00000007
p2 is not reached
Setpoint p2 “Pre-alarm” is not reached.
00000008
p4 exceeded
Setpoint p4“Maximum pressure – operation” is exceeded
00000009
p5 exceeded
Setpoint p5 “Maximum pressure – purging” is exceeded
0000000A
Temperature at sensor 1 is exceeded
Setpoint temperature at sensor 1 is exceeded
0000000B
Temperature at sensor 2 is exceeded
Setpoint temperature at sensor 2 exceeded
0000000C
Temperature at sensor 3 is exceeded
Setpoint temperature at sensor 3 exceeded