Maintenance and repair
Ex p control unit
Motor Purge Controller
Page 82 of 96
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Rev. 0
10.4.2.3
Alarm messages
Status
Code
Plain text
0000000D
Ex p inactive
The protected equipment is deactivated.
0000000E
Device fault 1
HW test error (processors)
0000000F
Device fault 2
HW test error (barriers)
00000010
Device fault 3
HW test error (internal temperature monitoring)
00000011
Device fault 4
HW test error (Severe error)
00000012
Sensor error 1
HW test error (Pressure sensor / Sensor board status)
00000013
Sensor error 2
HW test error (opt. current sensors)
00000014
Sensor error 3
HW test error (ext. temperature sensors)
00000015
p1 is not reached
Setpoint p1 “Min pressure” is not reached.
00000016
p3 is not reached
Setpoint p1 “Purging pressure” is not reached.
00000017
p4 is exceeded
Setpoint p4 “Maximum pressure - Operation” is exceeded.
00000018
p5 is exceeded
Setpoint p4 “Maximum pressure – Purging” is exceeded.
00000019
Temperature sensor 1 is exceeded
Setpoint temperature at sensor 1 is exceeded.
0000001A
Temperature sensor 2 is exceeded
Setpoint temperature at sensor 2 is exceeded.
0000001B
Temperature sensor 3 is exceeded
Setpoint temperature at sensor 3 is exceeded.