background image

Scope : 

USER MANUAL 
DE8-BC Ex d Complete Enclosure 

 

      

 

Date: 

20.03.2019 

Ver.: 

QA Code: 

5

 

Checked by: 

E.T. 

Approved by: 

S.Gr. 

Page: 

of 

Document no. : 

13614 

 
 

The passing on and copying of this document and the use or communication of it’s contents are forbidden without express authority. 
Offenders are liable to payment of damages. All rights are  reserved in the event of the registration of a patent . 

The DE8-BC range of Ex d enclosures are rugged and designed for harsh environment 
like: 

  Oil and gas industry 

  Chemical industry 

  Pharmaceutical 

  Industry 

  Agribusiness 

 

They are designed for use in potentially explosive atmospheres and certified according to the 
requirements of the ATEX Directive and IECEx. 

Marking

 

  
The enclosures listed in this manual are certified: 

            II 2 G / II 2 D  

The certificate numbers are :

 

INERIS 09ATEX0061X 
IECEx INE 13.0088X 

 

They are made in accordance with the following standards: 
 

Zones due to gases, vapors and fumes  

EN 60079-0 :  2018 

 

IEC 60079-0  : 2017 

EN 60079-1 :  2014 

 

IEC 60079-1  : 2014 

EN 60079-11: 2012 

 

IEC 60079-11: 2011 

 

Zones for dusts

 

EN 60079-31: 2014 

 

IEC 60079-31: 2013 

 
Description 

Our DE8-BC range of explosion proof enclosures is available in many sizes. They are made 
of welded and machined acid resistant stainless steel 316L or painted carbon steel. Each is 
expected  to  receive  electrical  components  inside,  making  service  and  maintenance  easy. 
They  can  also  be  customized  to  meet  each  individual  specific  need.  If  necessary,  multiple 
enclosures can be assembled on a frame with or without combined Ex e junction boxes. 
 
The    enclosures  can  be  delivered  fully  equipped  according  to  customer’s  requirements  or 
empty  with component certificate (U-certificate) to be used as basis for further certification of 
an Equipment or Protective System.  

Without Intrinsic safety 

With Intrinsic safety 

Ex db IIB T4 to T6 Gb  

Or 

Ex db IIB + H2 T4 to T6 Gb  

(Except for DE8-BC148) 

 

Ex tb IIIC IP65-66 T85°C to T135°C Db 

Ex db[ia] or [ib] IIB T6 Gb 

Or 

Ex db[ia] or [ib] IIB + H2 T4 to T6 Gb  

(Except for DE8-BC148) 

 

Ex tb [ia] IIIC IP65-66 T85°C Db 

Summary of Contents for DE8-BC

Page 1: ...Gr Page 1 of 7 Document no 13614 The passing on and copying of this document and the use or communication of it s contents are forbidden without express authority Offenders are liable to payment of d...

Page 2: ...apors and fumes EN 60079 0 2018 IEC 60079 0 2017 EN 60079 1 2014 IEC 60079 1 2014 EN 60079 11 2012 IEC 60079 11 2011 Zones for dusts EN 60079 31 2014 IEC 60079 31 2013 Description Our DE8 BC range of...

Page 3: ...rmation on the nameplate the explosive atmosphere present the area of use and ambient temperatures on surfaces Any damage on the device can cause the explosion proof protection to become ineffective T...

Page 4: ...of their documents of certification their certificates and with that after IS Circuits are cabled with connection wires of which the thickness of insulator is 0 5 mm and the section 0 5 mm The connec...

Page 5: ...er on the box using the original stainless steel bolts A4 70 minimum Ensure that all the bolts are screwed After tightening the bolts check with a shim of 15 100 mm 4 100mm for IIB H2 all around the f...

Page 6: ...O 3 NPT with welded ring M75 ISO References Per side A and C Per side B and D Max per perimeter Per side A and C Per side B and D Max per perimeter Per side A and C Per side B and D Max per perimeter...