Scope : 

USER MANUAL 
DE8-BC Ex d Complete Enclosure 

 

      

 

Date: 

20.03.2019 

Ver.: 

QA Code: 

5

 

Checked by: 

E.T. 

Approved by: 

S.Gr. 

Page: 

of 

Document no. : 

13614 

 
 

The passing on and copying of this document and the use or communication of it’s contents are forbidden without express authority. 
Offenders are liable to payment of damages. All rights are  reserved in the event of the registration of a patent . 

Packaging 

Location storage 

Duration storage 

Open 

In a covered location, clean (without contact with 
external substances) and closed with temperature a 
constant humidity (-40°C < T < +70°C). Shielded from 
important temperature variations 

2 years and more with regular inspection (cleanliness 
and mechanical damage) 

Putting into service 

  Verify  that  the  information  on  the  label  of  the  product  is  in  accordance  with  the 

permissible conditions for the Ex area of the site of use (Group II: Surface Industries - 
Category 2: high level of protection for ATEX G = for Gas / D = for Dust, IECEx EPL - 
G = for Gas / D = for Dusts -  IPxx: IP rating (waterproofness for solids and liquids)
 

 

  Check if there is a specific position of mounting 

  The wiring of the cable conductors must be made with a particular care 

  The  conductor  insulation  must  reach  the  terminal.  The  conductive  soul  must  not  be 

damaged 

  Not  to  exceed  the  authorized  maximal  temperature  appropriate  cables  must  be 

selected and take particular care installing them 

  Follow the instructions contained in the specifications 

 

Installation of intrinsic safety elements : 

o

  The  installation  of  the  intrinsic  safety  circuits  (IS)  inside  the  enclosure  is 

subordinated  to  the  respect  of  the  requirements  of  their  documents  of 
certification, their certificates and with that after: 

  IS  Circuits  are  cabled  with  connection  wires  of  which  the  thickness  of 

insulator is 

 0,5 mm and the section 

0,5 mm ² 

  The connection wires support a dielectric test of 500 V effective 

  The  air  gap  between  the  active  parts  under  voltage  of  the  connection 

elements  of  the  intrinsic  safety  circuit  compared  to  connection 
elements  of  an  non  intrinsic  safety  circuit  is  higher  or  equal  to  50 
millimeters 

  The air gap and creepage distances in the air between the active parts 

under  voltage  of  the  intrinsic  safety  circuit  compared  to  an  intrinsic 
safety circuit close are higher or equal to 6 millimeters 

  The air gap and creepage distances in the air between the active parts 

under voltage of the intrinsic safety circuit compared to the metal parts 
which can be with the ground are higher or equal to 3 millimeters 

  The active parts of the intrinsic safety circuits support a dielectric test of 

rigidity under an effective alternating voltage of 500 Volts compared to 
the metal mass 

  The active parts of an intrinsic safety circuit support a dielectric test of 

rigidity under an effective alternating voltage of 500 Volts compared to 
an intrinsic safety circuit close 

  Circuits NIS are cabled with conductive wires whose insulation is such 

as they can support a dielectric test of 2 U + 1000 V effective, U being 
the sum of the tensions of the IS and NIS circuits, with a minimum of 
1500 V 

Before starting 

  Make sure the unit has been correctly settled and not damaged 

  Make sure the wiring and the tightening of the terminal screws have been performed 

properly (see descriptive tightening torque) 

  The device may include any foreign body and no part is damaged 

  The cable gland must be tightened (see description of the gland torque) 

Summary of Contents for DE8-BC

Page 1: ...Gr Page 1 of 7 Document no 13614 The passing on and copying of this document and the use or communication of it s contents are forbidden without express authority Offenders are liable to payment of d...

Page 2: ...apors and fumes EN 60079 0 2018 IEC 60079 0 2017 EN 60079 1 2014 IEC 60079 1 2014 EN 60079 11 2012 IEC 60079 11 2011 Zones for dusts EN 60079 31 2014 IEC 60079 31 2013 Description Our DE8 BC range of...

Page 3: ...rmation on the nameplate the explosive atmosphere present the area of use and ambient temperatures on surfaces Any damage on the device can cause the explosion proof protection to become ineffective T...

Page 4: ...of their documents of certification their certificates and with that after IS Circuits are cabled with connection wires of which the thickness of insulator is 0 5 mm and the section 0 5 mm The connec...

Page 5: ...er on the box using the original stainless steel bolts A4 70 minimum Ensure that all the bolts are screwed After tightening the bolts check with a shim of 15 100 mm 4 100mm for IIB H2 all around the f...

Page 6: ...O 3 NPT with welded ring M75 ISO References Per side A and C Per side B and D Max per perimeter Per side A and C Per side B and D Max per perimeter Per side A and C Per side B and D Max per perimeter...

Page 7: ...insic safety elements a temperature probe must be fitted inside and be connected to a system that can switch off the supply when the inner temperature raises above the maximum ambient temperature indi...

Reviews: