Ex p Control Unit
SIEMENS Set
Commissioning
Rev. 0
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Page 55 of 80
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
8
Commissioning
DANGER
DEATH OR SERIOUS BODILY INJURY DUE TO CHANGES IN EX P RELEVANT
PARAMETERS.
Changing Ex p relevant parameters can put the system in a non-safe state.
The Ex p control unit from the SET SIEMENS is preset for the use of
the gas analyzers types OXYMAT 6F, ULTRAMAT 6F and CALOMAT 62F
and certificate SIEMENS TÜV 01 ATEX 1708X.
- The settings are preset for operation from one gas analyzer.
If the Ex p control unit is in programming mode (parameter
switch activated and password entered), the display of the
pressure values is in Pa. Settings are made in Pa.
General information
The user settings are limited to the additional settings such as messages,
optional sensors or display units, since the Ex p control itself is already preset
for operation.
*
= Setting is to be performed in case of automatic flushing
Start
Options
Settings
Temp.-Sensors
Temp-Sensor 1
Temp-Sensor 2
Temp-Sensor 3
Extended
Relays
Units
Sensors
Network
Functional test
Language
Settings backup
Parameter