POLARIS REMOTE
- for Zone 1/21
POLARIS Remote KVM Analog 15" / 19.1"
Installation
Technical data subject to change.
08/2019
EN 35/48
Single-sided shield connection on the connecting cables
Illustration 13: Example of single-sided shield connection
Connection of the shielding at one end only is recommended when there is inadequate
equipotential bonding, or none at all. In such cases an electrically isolated power supply
unit must be used. Before the equipment goes into service the directions from the
controller manufacturer regarding proper assembly and operation must be read carefully.