POLARIS REMOTE
- for Zone 1/21
POLARIS Remote KVM Analog 15" / 19.1"
Additional information
Technical data subject to change.
08/2019
EN 45/48
Mounting instructions Class D/E, CAT 6 Outlet
1.
Preperation of the Cable Ends
Remove cable sheathing approx. 50 mm in length. Cut back overall screen to
approximate 15 mm, remove twisted pair screen as required. To ensure contact
of the screen the diameter of the cable end must be 6 to 10 mm. If cable is too
thin fold back screen over cable cover. To improve contact wind self-adhesive
screening foil over the screen (approx. 2 turns, optional), bend tracing wire over
that.
2.
Mounting of the cables with one twin cable
clip
Both cables are mounted in the top cover with a
bolt through the cable clamp; this ensures
screen contact.
Strain relief with cable tie on top cover is
possible (not included in delivered state.)
3.
Recommendation – Colour Code
TIA/EIA-568-B
(Color sequence according
to DIN IEC 757)
colour
terminal
WH-OG
OG
1
2
WH-GN
GN
3
6
WH-BU
BU
5
4
WH-BN
BN
7
8