The CF card (4 GB) used is divided into:
Partition C
Size: approx. 2 GByte
boot drive with operating system protected by EWF
Partition D
Size: approx. 1.8 GByte
application data (BMS Graf Runtime) not protected by EWF
Behaviour when EWF is activated?
Partition C
When the EWF is activated, it is not possible to write on Partition C. All write accesses to
the C: partition are redirected into an RAM overlay. The changes that are made are not
available after rebooting.
Partition D
Is not protected by EWF. Write access to Partition D is possible at any time. The data is
still available after a reboot.
Data can be lost during write access if there is a power failure.
Procedure when changing system settings
ATTENTION
Switching off when the EWF is deactivated can cause a loss of data inside the
operating system!
Activate the EWF immediately after changes.
Shut down the operating system properly.
Deactivating the EWF
(1)
Select "CMD" in the START MENU.
(2)
Enter the
"ewfmgr c: /commitanddisable"
command line into the command
window.
(3)
Confirm with the Enter key.
(4)
Reboot the system.
(5)
Changes/settings can be made in the
operating system.