POLARIS PROFESSIONAL
- für Zone 1/21
POLARIS Panel PC Professional 10,4" / 12,1" / 12,1" W
Installation
Technical data subject to change.
04/2019
EN 23/68
6.
Installation
We recommend setting up and testing the entire system before its ultimate installation in
the ex-area. If a long connection cable is not available, please use a patch cable to test
the basic functions.
DANGER
Electrostatic charging through a stream of particles.
There is a risk of fatal injury in an explosive atmosphere!
Make sure there are no highly energetic charging mechanisms at the user
interface on the display unit or its accessories.
Do not install the device in the stream of particles.
DANGER
No PE connection. Risk of fatal injury in an explosive atmosphere!
The POLARIS must be integrated in the equipotential bonding.
The POLARIS Series is approved for an ambient temperature of from 0 °C to +50 °C
or from -20 °C to +60 °C and a relative air humidity of from 5 to 95 % without
condensation.
6.1
Requirements
–
The place where the POLARIS is installed must have sufficient mechanical
stability/fastening.
–
The enclosure intended for accommodating the POLARIS must be designed to
bear the device’s weight.
–
If a supporting system is used, the surface underneath and the means of fastening
the supporting system must be designed to bear the weight of the POLARIS
Selecting the location
CAUTION
Pay attention to wall and ground condition!
A sufficiently stable wall (e.g. concrete or limestone) or floor (e.g. concrete) must be
selected for securing the load-bearing system.
The structural stability of the wall or floor must be able to bear 4 times the weight
of the POLARIS as system solution.
The support arm system must be assembled using suitable mounting materials
(M12) (e.g. dowels or stud bolts).