background image

BARTINGTON INSTRUMENTS

 

Page 5 of 11 OM2298/3

The centres of the three vector sensors are superimposed; each orientation is denoted on the 
magnetometer’s label. The point of each vector arrow indicates the positive direction of each 
axis.

4.  Installing the Mag648 or Mag649

4.1. Siting the Magnetometer (Environment Recommendations)

Note: 

Site the magnetometer several metres from any magnetic base rock to avoid 

compromising measurements.

Note: 

Site the magnetometer several tens of metres from very large ferromagnetic objects 

that could become magnetised and create fields exceeding the measuring range of the 
sensor.

Note: 

Avoid siting the sensor near any ferromagnetic objects that may be subjected to the 

effects of magnetic hysteresis, which would affect the sensor in an unpredictable manner.

Note: 

For these reasons, a magnetic evaluation of any proposed installation site should be 

conducted to establish that it is free from magnetic contaminants. It is recommended that 
such an evaluation be carried out using total field or resonance magnetometers.

4.2. Cable Recommendations

The standard magnetometer provides differential output lines for analogue signal transmission. 
The advantages of this differential arrangement are very high common-mode noise rejection 
and the suitability of readily available cable types. Each of the two anti-phase output lines has 
low output impedance at the signal source, damping the lines and preventing ringing. Cable 
inductance and capacitance considerations require the cable to be terminated with a differential 
amplifier having a circa 50kΩ input impedance. This arrangement will provide some damping to 
high frequencies but will attenuate the signals above the frequency range of the sensor.

Due to these effects:

•  The cable pair loop resistance should not exceed 0.1 ohms per metre.

•  The pair loop inductance should not exceed 0.5 micro-Henry per metre.

•  The capacitance between should not exceed 52pF per metre.

•  The capacitance between conductors and shield should not exceed 120pF per metre.

To optimise operational life of underwater cables and avoid physical damage to the joint during 
handling:

Summary of Contents for Mag648

Page 1: ...Operation Manual for Mag648 and Mag649 Low Power Three Axis Magnetic Field Sensors...

Page 2: ...e Magnetometer Environment Recommendations 5 4 2 Cable Recommendations 5 4 3 Pre Installation Tests 6 4 4 Mounting Recommendations 7 4 5 Post Installation Testing 7 5 Using the Mag648 and Mag649 8 5 1...

Page 3: ...be disposed of safely to prevent unnecessary damage to the environment Note A note provides useful supporting information and sometimes suggests how to make better use of your purchase 2 Safe Use WARN...

Page 4: ...ltages in response to the magnitude and direction of the orthogonal components of a magnetic field A right hand co ordinate system is adopted see figure 1 In this system the X Y and Z axis correspond...

Page 5: ...d that such an evaluation be carried out using total field or resonance magnetometers 4 2 Cable Recommendations The standard magnetometer provides differential output lines for analogue signal transmi...

Page 6: ...the cables for continuity using an electrical continuity tester or ohmmeter a Test the cables end to end at the connectors to ensure the correct pins have been allocated to the conductors and there ar...

Page 7: ...to the connector or magnetometer When aligned correctly hand tighten the connector Refer to the product brochure for detailed information Note Other versions of the Mag648 and Mag649 have plug in type...

Page 8: ...Precautions Refer to the product brochure for maximum environmental electrical and mechanical ratings Caution Exceeding the maximum environmental ratings may cause irreparable damage to your sensor 6...

Page 9: ...elpdesk for further advice If repair is not advised replace with a new unit For information about disposal of the damaged unit refer to End of Life Disposal 7 Care and Maintenance Unpackaged versions...

Page 10: ...en to dispose of your magnetometer refer to the section on Troubleshooting 8 1 Waste Electrical and Electronic Equipment WEEE Regulations This product electrical and electronic equipment should not be...

Page 11: ...ton Instruments Limited in the following countries United Kingdom Australia Brazil Canada China European Union India Japan Norway and the United States of America Bartington Instruments Limited 5 Thor...

Reviews: