11
Dehumidify
The ClimateBoss has a dehumidification vent cycle. It consists of three programmable length
stages – a first exhaust stage, a heating stage, and a second exhaust stage. One, two, or all three stages
can be used. See page 15 for more information on programming the dehumidify mode.
Statistics
The ClimateBoss collects and stores temperature averages for 7 days for each zone respectively.
Each day it stores the average temperature for each operating stage (DIF, DAY, and NITE) and the
average for the 24 hours from the start of DIF until the end of NITE. To view, press the Zone 1 Daily
Averages or Zone 2 Daily Averages (only displayed in 2 zone mode).
Along with the averages, the ClimateBoss tracks the minimum and maximum temperatures for
each zone as well. The minimum/maximum temperatures will be stored until they are reset by pressing
the Reset Min/Max button on this screen. Run times for each output: Cools 1-4 and Heats 1-2 (Heat 3 if
activated), can be observed as well. Press the Run Times button to view. The Run Times will be stored
until reset by pressing the Reset button and the controller will display the number of days since the last
reset.
Settings
Zone 1 Low Alarm - Used to set the temperature for Zone 1 low alarm. Default = 32⁰F.
Zone 1 High Alarm - Used to set the temperature for Zone 1 high alarm. Default = 131⁰F.
Zone 2 Low Alarm - Used to set the temperature for Zone 2 low alarm. Default = 32⁰F.
(Only appears when the controller is set for 2 Zones.)
Zone 2 High Alarm - Used to set the temperature for Zone 2 high alarm. Default = 131⁰F.
(Only appears when the controller is set for 2 Zones.)
On to Auto Time –
Sets duration time in minutes for when all manually on outputs return to
auto. For more comfortable working conditions or if an emergency situation develops, any
output may be turned on manually. On to Auto will return any output that is set in the on
position after a certain length of time has expired. To disable the On-to-Auto time, set to 0.
Default = 15
Heat/Cool Delay – Sets the delay time (in minutes) when transitioning from cooling to
heating. Default = 10 minutes. Minimum = 0 minutes. Maximum = 30 minutes.
Thermistor Fail Mode – Determine what the controller will default to if a thermistor fail
error is detected. Setting to Off causes all outputs to turn off for the failed zone. Setting
to Heat puts the controller in a 50% on 50% off heating duty cycle. The 50/50 cycle is
designed for use during colder weather or in colder climates to prevent loss of crops.
Default = Heat.