background image

SANIDRY CSB INSTALLER'S AND OWNER'S MANUAL

2

SaniDry CSB Installer’s & Owner’s Manual

3

SaniDry CSB Installer’s & Owner’s Manual

4. Unit Assembly

4.1 Installing Feet (Optional)

Included with your SaniDry 
CSB are four leveling feet. It is 
important to level the unit for 
proper draining.  (See section 
5.1.4, Figure 6)

Installing Leveling Feet  

See Figures 2 and 2a for installing leveling feet.
1.  Lay down a protective pad (pillow, blanket, etc.).
2.   Carefully turn unit onto side opposite filter opening and drain 

port.

3.   Align leveling foot shaft with one of the four threaded hole 

locations as shown in Figure 2.

4.  Screw each leveling foot in ten revolutions.
5.  Carefully bring unit to upright position.
6.   Level unit for proper drainage as described in section 5.1.4 

(Figure 6) of this manual.

7.  Wait 10 minutes before operating.

 CAUTION!

Note: Operating the unit immediately after bringing it to an upright 
position can possibly damage the compressor. A short amount 
of time is needed to allow the oil to return to it’s reservoir for 
lubrication.

4.2 Drain Hose

Take drain hose off of drain port. With scissors, cut one inch off of 
hose end to eliminate dented area. Place drain hose end on drain 
port until fully seated. Refer to Section 5.1.4 regarding proper 
drainage.

5. Installation

5.1 Location

The SaniDry CSB can be installed in a variety oflocations to meet 
the owner’s needs, but should beinstalled directly in the area to be 
dehumidified. Other considerations include:

1.   Providing access to a 115 VAC power outlet (10' power cord 

is provided).

2.   Locating near a floor or other suitable drain (8' drain hose 

included).

3.   Do not install the SaniDry CSB with the intake or exhaust of 

the unit within 1' of a wall or other obstruction. Do not place 
the unit where curtains or debris can be drawn onto the 
intake and restrict airflow. Do not operate in standing water 
or place the unit near open water. Refer to Figure 5.

4.   The SaniDry CSB drains via a gravity system. A level 

indicator has been included near the intake of the unit. 
To ensure the unit will drain properly, the unit should be 
positioned so the level bubble appears in the non-shaded 
area of the level indicator as shown. Refer to Figure 6. If 
the unit is placed on an unlevel surface, adjust leveling feet 
using a crescent wrench or 7/16" open wrench. Move handle 
end of wrench from left to right to lower one foot. Adjust all 
four feet underneath the unit until bubble in the level dial is 
in the correct position. Failure to level the unit may result 
in leakage or improper drainage. See Section 4.2 regarding 
drain hose installation.

Figure 2: Insert leveling feet in 
locations

Figure 2a: Screw each leveling 
foot in ten revolutions

Figure 1: Four leveling feet

Figure 3: Drain port

Figure 2a: Drain hose position

Figure 5: Installing SaniDry CSB in area with proper clearance.

Figure 6: Level bubble should be in indicator area for proper drainage.

Summary of Contents for Sani Dry CSB

Page 1: ...Designed For Basement and Crawlspace Dehumidification INSTALLER S OWNER S MANUAL HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNER Copyright Basement Systems Inc TS 311b www basementsystems com...

Page 2: ...dehumidifier Read and Save These Instructions WARNING This symbol means important instructions Failure to heed them can result in serious injury or death CAUTION This symbol means important instructi...

Page 3: ...s but should beinstalled directly in the area to be dehumidified Other considerations include 1 Providing access to a 115 VAC power outlet 10 power cord is provided 2 Locating near a floor or other su...

Page 4: ...nt It turns off when the RH drops 5 below the set point Approximate Humidity Levels Per Setting Dry 35 to 45 Relative Humidity Normal 45 to 55 Relative Humidity Recommended for most applications Humid...

Page 5: ...ons below or on the tag located on the 1 4 pre filter CAUTION NOTE Failure to follow filter handling instructions may result in improper function of the dehumidifier and cause premature filter wear 7...

Page 6: ...ose connection in internal wiring 4 Humidity control is defective No dehumidification Compressor does not run but blower runs with fan switch AUTO and humidity control turned to ON 1 Defrost thermosta...

Page 7: ...er any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Res...

Page 8: ...y be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Basement Systems 2008 Basement Systems Inc All rights rese...

Reviews: