background image

 

CAUTION!

 

— This symbol means 

important instructions. failure to heed them can result 

in injury or material property damage.

2. inSTallaTion

2.1 location

The SaniDry XP is designed to be installed indoors and is ideal for 
unfinished and finished basements.

 

CAUTION!

•  installation outdoors, or near a pool or spa will void 

factory warranty. 

•  Do not use the dehumidifier as a bench or table.

2.1a in humid area, no ducting.

The simplest installation is to place the SaniDry XP in the humid 
area with no ducting. The air inlet on top & outlet on the side 
must be at least 1’ from walls and other obstructions to air 
flow.

2.1B in humid area, duct inlet and/or outlet.

If the humid area is very large or has high ceilings, 
dehumidification can be improved by adding an inlet and/or 
outlet duct to circulate and destratify stagnant areas. For a 
large area, add inlet or outlet ducting to create flow across the 
area’s greatest length. For areas with ceilings higher than 12’, 
use an inlet duct to draw warm, moist air from near the ceiling. 
See section 2.4 for attaching duct collars & ducting.

2.1C in a Remote area, Duct inlet & outlet. 

It is often desirable, in finished areas, to install the SaniDry 
XP in an adjacent equipment room or unfinished area. Air is 
transferred between the humid room and the unit via ducting. 
The factory-mounted humidity control on the SaniDry XP 
cabinet will sense the humidity in the humid room accurately 
enough with this installation method. 

2.1D in a Remote area, Duct outlet only. 

A simpler remote installation method than above uses ducting 
between the SaniDry XP discharge and the humid room; the 
SaniDry XP inlet draws air from the room in which it’s located. 
This works well if there is an adequate air flow path between the 
two rooms; i.e. high door undercut, louvered door or wall grill. 
There are several potential disadvantages to using this method. 
First, humid air is drawn into the room where the SaniDry XP is 
located. Second, to accurately sense humidity, the blower in the 
SaniDry XP may need to run continuously to draw air from the 
humid room into the SaniDry XP room. Third, a slight negative 
pressure is created in the room with the SaniDry XP which could 
backdraft open combustion devices located there. If such devices 
are present, call the factory for specific instructions before using 
this installation method or consider the option 2.1E below.

2.1e in a Remote area, Duct inlet only. 

When the SaniDry XP is located in a room separate from the 
main area to be dehumidified, it may be desirable to dehumidify 
and/or slightly pressurize that room. Pressurization assures 

that open combustion devices do not backdraft. This can be 
accomplished by installing a duct from the humid room to the 
SaniDry XP inlet and by allowing the SaniDry XP to discharge 
dehumidified air into the room in which it’s located. An 
adequate air flow path must exist between the two rooms for 
this method to work well. 

2.2 electrical Requirements

The SaniDry XP plugs into a common grounded outlet on a 15 Amp 
circuit. It draws between 6 and 7 Amps under normal operating 
conditions.

2.3 Condensate Removal

Condensate drains by gravity via the clear hose extending from 
the unit. Route hose to a floor drain, sump pump, or drainage 
system. Use care to keep the hose as flat to the floor as possible. 
Excessive humps or kinks will prevent proper drainage. 

If the SaniDry XP is located too far from a floor drain for the 
attached hose to reach, 1/2" PVC pipe can be used to extend 
it. It is commonly available in 10’ lengths from building supply, 
plumbing and hardware stores. It will slide tightly inside the end of 
the drain hose. 

If more than one length of pipe is required, they can be joined with 
a short piece cut from the end of the drain hose. 

2.4 Ducting

2.4a optional Ducting 

An inlet shroud with an 8" round collar and an 8" round 
exhaust collar are available from the factory that will allow 
round ducting to be attached to the inlet and/or outlet of the 
SaniDry XP.

2.4B Ducting for Dehumidification

Ducting the SaniDry XP as mentioned in sections 2.1B-2.1E 
requires consideration of the following points: 

 Duct Sizing:

 For total duct lengths up to 25 feet, use a 

minimum 8" diameter round or equivalent rectangular. For 
longer lengths, use a minimum 10" diameter or equivalent. 
Grills or diffusers on the duct ends must not excessively restrict 
air flow. 

isolated areas: 

Effective dehumidification may require 

that ducting be branched to isolated, stagnant areas. Use 6" 
diameter branch ducting to each of two or three areas, use 4" 
to each of four or more areas.

3. Dehumidifier operation

3.1 Humidity Control

The dehumidifier will run continuously until relative humidity 
(RH) is reduced to the desired humidity level using the electronic 
controller. Setting the electronic humidity controller to lower RH 
levels will 

noT

 increase the unit’s dehumidification rate - it will 

simply run longer to reduce the area’s RH to the setting. The 
SaniDry XP unit (and refrigerant based dehumidifiers in general) 
will reduce a warm space’s RH to a lower level than that of a cool 
space. For example, the SaniDry XP may reduce an 80° F space to 
30% RH. However, if the same space is 65° F, it may only reduce 
it to 40% RH. It is therefore pointless to set the electronic humidity 

SaniDry XP INSTALLER'S AND OWNER'S MANUAL

3

SaniDry XP Installer’s & Owner’s Manual

Summary of Contents for SD109 SaniDry XP

Page 1: ......

Page 2: ...the Sensors 5 8 8A Coil Sensor 5 8 8B Humidity Sensor 5 9 Other Functions 5 9 1 Control Lock 5 9 2 Display Coil Temperature 5 10 Electromagnetic Compatible Standard 5 10 1 EMS Criteria 5 10 2 EMC Crit...

Page 3: ...om Pressurization assures that open combustion devices do not backdraft This can be accomplished by installing a duct from the humid room to the SaniDry XP inlet and by allowing the SaniDry XP to disc...

Page 4: ...in the mode previously selected 7 OPERATING MODES 7 1 POWER UP When the unit is powered up it will be in STANDBY MODE indicated by the flashing RED RUN LED All other LEDs are extinguished None of the...

Page 5: ...DEFROST CYCLE every 53 minutes of operation 8 8B HUMIDITY SENSOR When the humidity sensor s output voltage is less than 0 5V or more than 4V the control unit considers it faulty and will display E2 i...

Page 6: ...efrigerant liquid then passes through a filter drier and capillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the...

Page 7: ...porator 1 SS 0 6mm 31 Tubing evaporator 1 9 52mm OD x 8mm wall copper tubing 32 Grommet 1 Buna N 33 Capillary 2 2 5mm OD x 1 0mm wall 34 Tubing discharge 1 6 35mm OD x 8mm wall copper tubing 35 Filter...

Page 8: ...SaniDry XP SERVICE PARTS LIST To order contact your local Basement Systems Dealer 8 SaniDry XP Installer s Owner s Manual Exploded View...

Page 9: ...edrilled mounting holes are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against t...

Page 10: ...x and bend the tabs in 6 Place the collar over the blower outlet and line up the tabs with the holes in the cabinet 7 Using 4 screws from the kit attach the collar to the unit collar Ductable Inlet Ex...

Page 11: ...nty claim to BSI such that BSI receives such claim prior to the end of the applicable warranty period BSI shall have no obligation hereunder with respect to any claim received by BSI after the expirat...

Reviews: