BE1-51/27C Tests and Adjustments
5-16
Step 9. Reconnect the output to the neutral current sense terminals. See Figures 5-3, 5-5, or 5-6.
Step 10. Set the front panel
INST 1 (NEUTRAL)
control to a position approximating the desired neutral
instantaneous 1 overcurrent pickup point for the relay.
Step 11 Apply current to the relay.
Step 12 Rapidly increase the overcurrent input to the relay until the instantaneous output relay just
energizes. Note the test set overcurrent threshold reading on the ammeter.
Step 13. Remove the input current.
Step 14. Reset the
INST TARGET
(if present).
Step 15. If the overcurrent threshold reading from Step 13 was too high or low, adjust the front panel
INST
1 (NEUTRAL)
Control CCW to lower (or CW to raise) the Neutral Instantaneous 1 Overcurrent
Pickup Point. Repeat Steps 9 through 14. If
NOT
, proceed to the next test.
INST 2 Control Setting
For this adjustment, repeat INST 1 control setting, but substitute instantaneous 2 output terminals (11 and
12) and the front panel
INST 2
controls Because neutral sensing does not apply to this pickup point, ignore
Steps 9 through 15.