4-8
BE1-24 Installation
NOTE
Be sure the relay case is hard-wired to earth ground with no smaller than 12 AWG copper
wire attached to the ground terminal on the rear of the relay case. When the relay is
configured in a system with other protective devices, it is recommended to use a separate
lead to the ground bus from each relay.
CONNECTIONS
Incorrect wiring may result in damage to the relay. Be sure to check model and style number against the
options listed in the Style Number Identification Chart before connecting and energizing a particular relay.
Connections should be made with minimum wire size of 14 AWG except as noted for
the ground wire. Typical internal connections are shown in Figure 4-7. Typical AC
sensing connections are shown in Figure 4-8, and a typical control circuit diagram is
shown in Figure 4-9.
Summary of Contents for BE1-24
Page 9: ...1 4 BE1 24 General Information Figure 1 1 Inverse Square vs Two Step...
Page 10: ...BE1 24 General Information 1 5 Figure 1 2 Protection Characteristics of the BE1 24...
Page 12: ...BE1 24 General Information 1 7 Figure 1 3 Style Number Identification Chart...
Page 16: ...BE1 24 General Information 1 11 Figure 1 4 Inverse Square Characteristic Curves...
Page 19: ...2 2 BE1 24 Human Machine Interface Figure 2 1 Location of Controls and Indicators...
Page 27: ...4 2 BE1 24 Installation Figure 4 1 M1 Case Outline Dimensions Front View...
Page 30: ...BE1 24 Installation 4 5 Figure 4 4 M1 Case Double Ended Panel Drilling Diagram Rear View...
Page 31: ...4 6 BE1 24 Installation Figure 4 5 M1 Case Panel Drilling Diagram...
Page 32: ...BE1 24 Installation 4 7 Figure 4 6 M1 Case Projection Mounting Outline Dimensions Rear View...
Page 34: ...BE1 24 Installation 4 9 Figure 4 7 Typical Internal Connections...