M
Actual V/Hz condition
V/Hz Setting
BE1-24 Testing
5-3
Figure 5-1. Test Setup Diagram
Instantaneous Time Verification
Step 1.
Connect the unit as shown in Figure 5-1.
Step 2.
Adjust the front panel thumbwheel switches as follows:
• INST. PICKUP
- 2.00 V/Hz
• TIME TRIP PICKUP
- 2.00 V/Hz
• TIME DIAL
- 0.1
• RESET
- 0.1
• ALARM PICKUP
- 2.00 V/Hz
• ALARM TIME DELAY - 0.0
Step 3.
Apply 180 Vac at 60 Hz to the unit under test (M = 1.5). Measure and record the interval
from initiation of input condition to instantaneous output contact transition. Verify that the
recorded time is less than eight cycles.