BE1-24 Testing
5-5
Step 4.
Repeat step 3 for TIME DIAL settings of 1.0 and 0.0. Elapsed times should be as follows.
Setting
Elapsed Time
1.0
20 ±3 seconds
0.0
200 ±20 seconds
Step 5.
Repeat steps 3 and 4 with input conditions of 180 Vac at 60 Hz (M = 1.5).
Elapsed times should be as follows.
Setting
Elapsed Time
0.1
0.45 ±0.5 seconds
1.0
3.7 ±0.4 seconds
0.0
36 ±4 seconds
This completes the operational test procedures.