BE1-25 General Information
1-11
Line and Bus Voltage
Monitor Option
Range
Continuously adjustable over the range of 10 to 135 Vac.
Accuracy
The line and bus voltage setpoints do not vary more than 3% from
a reference measurement at 25
°
C, with nominal input frequency,
and with temperature and voltage inputs within specified operating
range. Setpoints do not vary more than 1% from a reading at 25
°
C
over the limited temperature range of +15 to +40
°
C.
Isolation
In accordance with IEC 255-5 and IEEE C37.90, one minute dielectric
(high potential) tests as follows:
All circuits to ground:
2121 Vdc
Input to output circuits: 1500 Vac or 2121 Vdc
Surge Withstand Capability
Oscillatory
Fast Transient
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems.
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems.
Radio Frequency
Interference (RFI)
Maintains proper operation when tested in accordance with IEEE
C37.90-1989,
Trial-Use Standard Withstand Capability of Relay
Systems to Radiated Electromagnetic Interference from
Transceivers.
UL Recognition
UL recognized per Standard 508, UL File No. E97033. Note:
Output contacts are not UL recognized for voltages greater than
250 V.
Shock
In standard tests, the relay has withstood 15g in each of three
perpendicular planes without structural damage or degradation of
performance.
Vibration
In standard tests, the relay has withstood 2g in each of three
mutually perpendicular axes swept over the range of 10 to 500
hertz for a total of six sweeps, 15 minutes each sweep, without
structural damage or degradation of performance.
Operating Temperature
-40
°
C (-40
°
F) to 70
°
C (158
°
F).
Storage Temperature
-65
°
C (-85
°
F) to 100
°
C (212
°
F).
Weight
13.7 pounds maximum.
Case Size
S1