BE1-25 Human-Machine Interface
2-5
Callout
Control or Indicator
Function
S
(Cont'd)
WARNING!
If relay has Output Option G or H:
Condition Switch No. 2 (LL-LB) may be
Down (ON) only when output option G or H
has been selected and the Voltage Monitor
Output contacts do not by-pass the Sync-
Check contact. Use of the external LL-LB
switch (if installed) is similarly limited..
No. 3 (Dead Line/Live
Bus)
Up = OFF
If relay has Output Option E or F:
The ON (Down) position causes immediate closure of
the Sync Output contact, if a dead line/live bus
condition is detected with the breaker open.
If relay has Output Option G or H:
The ON (Down) position causes immediate actuation of
the Voltage Monitor relay, if a dead line/live bus
condition is detected with the breaker open.
No. 4 (Live Line/Dead
Bus)
Up = OFF
If relay has Output Option E or F:
The ON (Down) position causes immediate closure of
the Sync Output contact, if a live line/dead bus
condition is detected with the breaker open.
If relay has Output Option G or H:
The ON (Down) position causes immediate actuation of
the Voltage Monitor relay, if a live line/dead bus
condition is detected with the breaker open.