background image

BE1-32R, BE1-32R O/U

3

APPLICATION

(continued)

When the generator is paralleled and loaded, the kW

signal will decrease by the amount of load the generator

accepted. An underpower relay can measure utility

power and generate a “stop” signal when utility power

decreased below a selected level. A definite time delay

will generally be provided for the “stop” signal of one

minute or more. The Basler Model BE1-32 O/U Power

Relay incorporates both over and under power sensing

in one relay, which makes it ideal for this application.

In the second configuration (Figure 3) the “start” signal

is generated as in that of Figure 2. The setpoint of the

start signal should be above the import power setting.

The “stop” signal will require an underpower relay on

the generator output. This system is illustrated in Figure

3.

EXAMPLE 3 - GENERATOR OVERLOAD

Refer to Figure 3. Whenever excessive load has been

connected to a generating system, the Power Relay will

initiate the corrective action by energizing an alarm to

alert the station operator or will initiate an automatic

sequence to either shed non-critical load or start and

parallel an in-house generator to assume the excess

load.

EXAMPLE 4 - DISTRIBUTION SYSTEM OVERLOAD

Another typical use, addressing excessive load, con-

cerns distribution protection, see Figure 4. A high-

voltage bus supplies two transformers. T1 and T2

together can supply all connected load. However,

neither T1 or T2 is capable of supplying the total load.

To provide adequate protection for the distribution

system, the overpower function is used to sense

overload conditions on each transformer and the

underpower function is used to sense power flowing

through the transformers in an undesired direction.

Figure 3 - Power Relay Start/Stop Control

EXAMPLE 5 - REACTIVE POWER (VARs)

DETECTION

This example deals with the Directional Power Relay’s

ability to measure real or reactive power.

Real power (watts) is supplied to the generator by the

prime mover, and reactive power (vars) is supplied to

the field by the exciter. When field excitation is signifi-

cantly reduced and the connected system can provide

sufficient reactive power to maintain the generator’s

terminal voltage, reactive power will flow into the

machine and cause it to operate as an induction

generator with essentially the same kW output. This

situation causes problems; first, the additional reactive

loading of the faulty generator must be redistributed to

other synchronous generators on the system. Sec-

ondly, a synchronous generator is not designed to

function as an induction generator. Excessive heating

occurs in the damper (Amortisseur) windings, slot

wedges, and in the surface iron of the rotor due to slip

frequency current flow which results when a synchro-

nous generator is operated as an induction generator.

The Directional Power Relay can be applied to respond

to this reactive power flow.

The Basler BE1-32 Directional Power Relay is designed

to respond to true power as defined by the equation:

P = El cos 

Θ

where: P = real power (watts)

E = effective emf or system voltage

I = effective current

Θ

 = the phase angle between E and I

Figure 4 - Distribution Protection

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: