background image

6

BE1-32R, BE1-32R O/U

SPECIFICATIONS

(continued)

Type D Sensing: Three-Phase (Figure 10). The type D

sensing configuration monitors three line-to-neutral

voltages and three phase currents of a three-phase, four-

wire circuit and calculates the power flowing in the

tripping direction. Relays with this sensing type are

calibrated in three-phase watts.

Type E Sensing: Three-Phase (Figure 11). The type E

sensing configuration monitors three line-to-line voltages

and two of the phase currents of a three-phase, three-

wire circuit and calculates the power flowing in the

tripping direction. The power equation assumes that

conditions are balanced. Relays with this sensing type

are calibrated in three-phase watts. Note: Type E

configurations are phase rotation sensitive.

Power Supply

One of five power supply boxes may be selected to

provide internal operating power. They are described in

Table 1.

POWER RANGE PICKUP

Overpower pickup of the relay is adjustable by means of

a front panel 10 position rotary TAP select switch used in

conjunction with the front panel HIGH/LOW switch over

the defined ranges listed in Table 2. Underpower pickup

is continuously adjustable from 10 to 95% of the selected

overpower tap. Pickup accuracy is within 2% (or 0.05

watts) of the front panel setting for unity power factor.

Pickup accuracy is within 5% of the front panel setting for

all other power factors between 0.9 and 0.5. The range of

voltage for proper operation is 40 to 150 percent of the

nominal value.

When the calculated value for power exceeds the over-

power pickup setting or falls below the underpower

pickup setting and is in the tripping direction, the appro-

priate LED is illuminated and timing is initiated. One

indicating LED is provided for each measuring function

within the relay.

KW TRANSDUCER

The kW Transducer samples the current and voltage of

each phase on a continuous basis. The resulting signals

representing current and voltage are multiplied and

integrated to develop a dc voltage level that is representa-

tive of true kW.

COMPARATOR CIRCUITS

The dc output of the kW Transducer is then compared to

front panel settings for underpower and/or overpower.

When the reference level of the comparator (or compara-

tors if applicable) is crossed, the output of the compara-

tor is used to either energize the appropriate output (if

instantaneous timing has been specified) or to initiate the

timing circuits (definite, or inverse).

TIMING

Time delay is defined as the elapsed time between the

application of the condition to the input terminals of the

relay and the transition of the output contacts.

† Type R Power Supply may require 14 Vdc to begin operation. Once operating, the

   voltage may be reduced to 12 Vdc.

‡ Type S Power Supply is field selectable for 48 or 125 Vdc. Selection must be

   implemented at time of installation. This Power Supply option is factory set for 125 Vdc.

Table 1 - Power Supply Options

Figure 10 - Three Phase, Type D Sensing

Figure 11 - Three Phase, Type E Sensing

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: