background image

BE1-32R, BE1-32R O/U

7

SPECIFICATIONS

(continued)

Each model, BE1-32R or BE1-32 O/U is capable of

instantaneous trip, definite time delay trip, or an inverse

time delayed trip as defined and selected by the Style

Chart.

Instantaneous response time of the relay is within 80

ms (60 Hz) or 100 ms (50 Hz) for a real power magni-

tude of 2 times the setting.

The definite time delay is adjustable over the ranges of

0.1 to 9.9 seconds and 01 to 99 seconds. Selection of

the ranges is accomplished by a front-panel multiplier

switch which selects either 0.1 or 1.0 as a multiplier of

the front panel Time Dial thumbwheel switch. (A Time

Dial setting of 00 enables instantaneous operation.)

Definite timing accuracy is ±5% of the setting or 50 ms,

whichever is greater.

Inverse time delayed trip is available for the overpower

function only. The inverse time delay curve is adjust-

able from 01 to 99 by means of a front-panel

thumbwheel switch. Incrementing the thumbwheel

switch moves the inverse curve along the vertical axis.

(See Figure 12 for Inverse Time Characteristics.) A

Time Dial setting of 00 enables instantaneous opera-

tion. Inverse time is accurate to within ±5% of the

published curve or 50 ms, whichever is greater.

POWER SUPPLY STATUS OUTPUT (OPTIONAL)

The power supply status output relay is energized and

its NC output contact is opened when power is applied

to the relay. Normal internal relay operating voltage

maintains the power supply status output relay continu-

ously energized with its output contact open. If the

power supply output voltage falls below the require-

ments of proper operation, the power supply output

relay is deenergized, closing the NC output contact.

Table 2 - Power Range Pickup Settings

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: