BE1-40Q Functional Description
Power Supply
Basler Electric enhanced the power supply design for unit case relays. This new design created three, wide
range power supplies that replace the five previous power supplies. Style number identifiers for these power
supplies have not been changed so that customers may order the same style numbers that they ordered
previously. The first newly designed power supplies were installed in unit case relays with EIA date codes
9638 (third week of September 1996). Relays with a serial number that consists of one alpha character
followed by eight numerical characters also have the new wide range power supplies. A benefit of this new
design increases the power supply operating ranges such that the 48/125 volt selector is no longer
necessary. Specific voltage ranges for the three new power supplies and a cross reference to the style
number identifiers are shown in the following table.
Table 3-1. Wide Range Power Supply Voltage Ranges
Power Supply
Style Chart Identifiers
Nominal Voltage
Voltage Range
Low Range
R
24 Vdc
12
†
to 32 Vdc
Mid Range
O, P, S
48, 125 Vdc,
120 Vac
24 to 150 Vdc,
90 to 132 Vac
High Range
T
125, 250 Vdc,
120, 240 Vac
62 to 280 Vdc,
90 to 270 Vac
†
14 Vdc is required to start the power supply.
Relay operating power is developed by the wide range, isolated, low burden, flyback switching, solid state
power supply. Nominal ±12 Vdc is delivered to the relay internal circuitry. Input (source voltage) for the
power supply is not polarity sensitive. A red LED turns ON to indicate that the power supply is functioning
properly.
Power Supply Status Output
A normally closed output relay may be provided, whose contact remains open when energized by the
presence of nominal voltage at the output of the power supply. If the power supply voltage fails or falls
below requirements, the power supply status output relay will deenergize, closing its contact.
A shorting bar is included in the relay case so that the status output terminals can provide a remote
indication that the BE1-40Q Relay has been withdrawn from its case or taken out of service by removing the
connection plug.
If the power supply status output is provided, then auxiliary output contacts are not available.
Summary of Contents for BE1-40Q
Page 13: ...2 2 BE1 40Q Human Machine Interface Figure 2 1 Location of Controls and Indicators ...
Page 19: ...4 2 BE1 40Q Installation 2 02 01 D1427 01 Figure 4 1 S1 Case Outline Dimensions Front View ...
Page 22: ...BE1 40Q Installation 4 5 Figure 4 6 S1 Case Outline Dimensions Rear View ...
Page 25: ...4 8 BE1 40Q Installation Figure 4 10 Sensing Input Connections Figure 4 11 Output Connections ...
Page 35: ...5 8 BE1 40Q Setting and Testing Figure 5 4 Blank Graph ...