5-4
BE1-40Q Setting and Testing
pickup
"
V
relay
3
×
I
relay
(4.5)
NOTE
The test current given in Table 5-2, below, is twice the pickup current.
Step 8.
Note the indicated voltage and current, and calculate the actual pickup value as defined by:
Compare the result with Table 1-1. Reset the target indicator, if present.
Step 9.
Repeat Steps 7 and 8 for each TAP setting, verifying both the HI and LOW RANGE setpoints. The
pickup tolerance should be ±2% of the front panel setting or 0.1 var, whichever is greater.
Timing Verification
Step 1.
Connect the test circuit as shown in Figure 5-2.
Step 2.
Connect a timer to record the time interval from application of the test current that will be applied
in Step 6, to the change of state of the output relay. If a normally open contact has been selected,
a trip will occur when the contact closes; normally closed contacts will open to trip.
Step 3.
Make the following front panel adjustments on the BE1-40Q Relay:
RANGE Switch - LOW position
TAP Switch - Position A (minimum)
TIME DELAY Switches - 10 (1.0 second)
Step 4.
Apply appropriate operating power, depending on the power supply option, to terminals 3 and 4.
The POWER LED should light.
Step 5.
Adjust the voltage source to the nominal value of the sensing input as designated by the second
digit of the style number.
Step 6.
Adjust the current source to produce a 60
!
lagging current that steps from zero magnitude to the
test current value shown in Table 5-2.
Table 5-2. Test Current
Second Digit
of Style Number
Nominal
Ac Voltage
Pickup
Current
Test Current
3
120
0.361 A
0.722 A
6
208
0.416 A
0.832 A
9
240
0.361 A
0.722 A
Step 7.
The actual time delay should be 1.0 second ±5%.
Step 8.
Adjust the TIME DELAY Switches to a setting of 55 (5.5 seconds), and repeat Steps 6 and
7. The time delay should be 5.5 seconds ±5%.
Step 9.
Adjust the TIME DELAY Switches to a setting of 99 (9.9 seconds), and repeat Steps 6 and
7. The time delay should be 9.9 seconds ±5%.
Relay Characteristics Verification
Preliminary
Step 1.
Connect the test circuit as shown in Figure 5-2.
Summary of Contents for BE1-40Q
Page 13: ...2 2 BE1 40Q Human Machine Interface Figure 2 1 Location of Controls and Indicators ...
Page 19: ...4 2 BE1 40Q Installation 2 02 01 D1427 01 Figure 4 1 S1 Case Outline Dimensions Front View ...
Page 22: ...BE1 40Q Installation 4 5 Figure 4 6 S1 Case Outline Dimensions Rear View ...
Page 25: ...4 8 BE1 40Q Installation Figure 4 10 Sensing Input Connections Figure 4 11 Output Connections ...
Page 35: ...5 8 BE1 40Q Setting and Testing Figure 5 4 Blank Graph ...