BE1-47N General Information
1-5
Outputs
Output contacts are rated as follows:
Resistive
120/240 Vac - Make 30 A for 0.2 seconds, carry 7 A continuously,
and break 7 A.
250 Vdc - Make and carry 30 A for 0.2 seconds, carry 7 A
continuously, and break 0.3 A.
500 Vdc - Make and carry 15 A for 0.2 seconds, carry 7 A
continuously, and break 0.1 A.
Inductive
120/240 Vac, 125/250 Vdc - Make and carry 30 A for 0.2
seconds, carry 7 A continuously, and break 0.3 A (L/R = 0.04).
Shock
In standard tests, the relay has withstood 15 g in each of three
mutually perpendicular planes without structural damage or
degradation of performance.
Vibration
In standard tests, the relay has withstood 2 g in each of three
mutually perpendicular planes, swept over the range of 10 to 500
hertz for a total of six sweeps, 15 minutes each sweep, without
structural damage or degradation of performance.
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one
minute dielectric (high potential) tests as follows:
All circuits to ground:
2121 Vdc
Input to output circuits:
1500 Vac or 2121 Vdc
UL Recognized
UL Recognized per Standard 508, UL File No. E97033. Note:
Output contacts are not UL Recognized for voltages greater than
250 volts.
Radio Frequency Interference
(RFI)
Maintains proper operation when tested for interference in
accordance with IECC C37.90-1989, Trial-Use Standard
Withstand Capability of Relay systems to Radiated
electromagnetic Interference from Transceivers.
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge
Withstand Capability (SWC) Tests for Protective Relays and
Relay Systems.
Fast Transient
Qualified to ANSI/IEEE C.37.90.1-198X,
Impulse Test
Qualified to IEC 255-5.
Temperature
Operating
Storage
-40
(
C (-40
(
F) to 70
(
C (158
(
F)
-65
(
C (-85
(
F) to 100
(
C (212
(
F)
Weight
14.0 pounds
Case Size
S1
www
. ElectricalPartManuals