BE1-50/51M-222 Controls and Indicators
2-2
RELAY
OVERCURRENT
BE1-50/51M-222
S
T
U
I
N
+
T
E
N
S
S
T
I
N
U
+
E
N
T
T
H
S
S
H
T
T
N
E
+
U
N
I
T
S
(0.5 MIN. SET)
PICKUP
DIAL
PICKUP
MANUAL TRIP
TIME
MANUAL TRIP
PICKUP
0
0
0
0
0
Highland, Illinois
Basler Electric
R
S
0
CURVE
INST
TIME
RESET
D2644-13
08-18-97
C
D
E
A
B
I
H
G
F
Table 2-1. BE1-50/51M-222 Controls and Indicators - Continued
Locator
Control or Indicator
Function
J -
Continue
d
SW8-4
Provides selection of either instantaneous or integrating
reset characteristic. Closing SW8-4 provides integrating
reset. Opening SW8-4 provides instantaneous reset.
K
Auxiliary Output Jumper
Terminations
Configures the auxiliary output contacts to close with
either the instantaneous (50) trip and/or the timed (51)
trip.
Jumper E2 to E1A to close the auxiliary contact with the
timed (51) trip. This jumper is yellow and factory installed
to close the auxiliary output contacts with the timed trip.
Jumper E3 to E1B to close the auxiliary contact with the
instantaneous (50) trip. This jumper is blue and factory
installed to close the auxiliary output contacts with the
instantaneous trip.
Figure 2-1. BE1-50/51M-222, Location of Controls and Indicators
Summary of Contents for BE1-50/51M-222
Page 29: ...BE1 50 51M 222 Installation 4 2 Figure 4 1 Outline Dimensions C1 Case ...
Page 30: ...BE1 50 51M 222 Installation 4 3 Figure 4 2 Panel Drilling Diagram C1 Case ...
Page 32: ...BE1 50 51M 222 Installation 4 5 Figure 4 4 DC Control Connections ...
Page 33: ...BE1 50 51M 222 Installation 4 6 Figure 4 5 BE1 50 51M 222 Overcurrent Relay Rear View ...