BE1-50/51M-222 Functional Description
3-2
CAUTION
Trip circuit voltage is present at the front panel test points. When shorting the test
points, use insulated jumpers to avoid contact with these voltages.
P O W E R
C T
S U P P L Y
P O W E R
B R I D G E
C T
S I G N A L
T I M E
S C A L E
I N S T
S C A L E
M U X
S W
S W
S W
S W
T I M E
P I C K U P
I N S T
P I C K U P
S W
S W
S W
D O G
W A T C H
S U P E R V I S O R
M I C R O
5 1
5 0
T I M E
D I A L
T I M E
C U R V E
50/60 Hz
I N S T D E L A Y
T P
T P
A U X
I S O L A T I O N
T A R G E T S
M A G N E T I C
T I M E
P I C K U P
5 1
5 0
I N P U T
G N D
D 2 1 0 6 - 1 3
08-15-97
2
3
6
5
4
7
8
9
A N D
A / D
C O N V E R T E R
P O W E R - O F F
S E N S I N G
S W
R E S E T C H A R .
5 1
5 0
The microprocessor performs the program operations based on the inputs and the internal software
program. When the sensed current exceeds the TIME PICKUP setting, the TIME PICKUP LED is turned
ON. TIME contacts (51 and 51 AUX) are closed in accordance with the time characteristic curve. If the
sensed current exceeds the INST PICKUP setting, the INST contacts (50) are closed.
Power-Off Sensing
The power-off sensing circuits measure the decaying voltage to determine the length of time that power is
removed (zero current). This provides information for the integrating reset function even when power has
been entirely removed.
Outputs
Instantaneous And Timed
System circuit breakers controlled by the output contacts can be manually tripped by applying a short across
the TIME or INST MANUAL TRIP front panel test points. Current flow in the trip circuit is indicated by the
operation of the target. The targets will not operate without adequate operating power for the relay.
Auxiliary
The auxiliary output contacts can be configured by the user to close when the timed and/or instantaneous
trip occurs. With both jumpers installed (this is the factory setting) either the timed or instantaneous trip
closes the auxiliary contacts.
Figure 3-1. Functional Block Diagram
Summary of Contents for BE1-50/51M-222
Page 29: ...BE1 50 51M 222 Installation 4 2 Figure 4 1 Outline Dimensions C1 Case ...
Page 30: ...BE1 50 51M 222 Installation 4 3 Figure 4 2 Panel Drilling Diagram C1 Case ...
Page 32: ...BE1 50 51M 222 Installation 4 5 Figure 4 4 DC Control Connections ...
Page 33: ...BE1 50 51M 222 Installation 4 6 Figure 4 5 BE1 50 51M 222 Overcurrent Relay Rear View ...