background image

BE1-50/51M-222 Testing

5-5

CAUTION

Trip circuit voltage is present at the front panel test points.  When shorting the test
points, use insulated jumpers to avoid contact with these voltages.

Manual Trip Test

Perform preliminary setup:

Connect test setup as shown in Figure 5-2.

Insure that SW8 switches are set correctly: SW8-1 for operating frequency, SW8-2 to OFF (no
instantaneous delay), SW8-3 to OFF (no instantaneous delay), and SW8-4 to OFF (selects
instantaneous reset).

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 1.0.

Set INST PICKUP to 01.

Step 1. Set target current source to 1.0 ampere, ac.

Step 2. Apply 0.9 ampere input current to terminals 8 and 9.

Step 3. Connect a jumper between TIME MANUAL TRIP test points.  Check that TIME target operates.

Step 4. Connect a jumper between INST MANUAL TRIP test points.  Check that INST target operates.

Step 5. Reset targets.

Integrating Reset Test

Perform preliminary setup:

Insure that SW8 switches are set correctly: SW8-1 for operating frequency, SW8-2 to OFF (no
instantaneous delay), SW8-3 to OFF (no instantaneous delay), and SW8-4 to ON (selects integrating
reset).

Set TIME DIAL to 4.5.

Set CURVE to I.

Set TIME PICKUP to 1.0.

Set INST PICKUP to 90.

Step 1. Set target current source to 1.0 ampere, ac.

Step 2. Read all of Step 3 before beginning Step 3.

Step 3. Apply 4.0 amperes input current to terminals 8 and 9.  After the unit trips, remove the input current

for 20 ±0.25 seconds, then reapply the 4.0 amperes input current.  Record the elapsed time from
the reapplication of input current to the output retrip.

Result:  Elapsed time should be 1.55 ±0.3 seconds.

Summary of Contents for BE1-50/51M-222

Page 1: ... T N E U N I T S 0 5 MIN SET PICKUP DIAL PICKUP MANUAL TRIP TIME MANUAL TRIP PICKUP 0 0 0 0 0 Highland Illinois Basler Electric R S 0 CURVE INST TIME RESET D2644 12 08 18 97 INSTRUCTION MANUAL FOR OVERCURRENT RELAY BE1 50 51M 222 Publication Number 9 2520 00 984 Revision A 12 99 ...

Page 2: ...rm the procedures presented in this manual INTRODUCTION This manual provides information concerning the operation and installation of the BE1 50 51M 222 Overcurrent Relay To accomplish this the following is provided Specifications Functional description Mounting information Setting procedure example ...

Page 3: ... Basler Electric Co Highland IL 62249 December 1999 It is not the intention of this manual to cover all details and variations in equipment nor does this manual provide data for every possible contingency regarding installation or operation The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electr...

Page 4: ...essor 3 1 Power Off Sensing 3 2 Outputs 3 2 SECTION 4 INSTALLATION 4 1 General 4 1 Dielectric Test 4 1 Mounting 4 1 Outline Dimensions 4 2 Panel Drilling Diagram C1 Case 4 3 Connections 4 4 AC Input Connections 4 4 DC Control Connections 4 5 BE1 50 51M 222 Overcurrent Relay Rear View 4 6 SECTION 5 TESTING 5 1 General 5 1 Dielectric Test 5 1 Operational Test Procedure 5 1 Test Equipment Required 5 ...

Page 5: ...iv CONTENTS Continued SECTION 6 MAINTENANCE 6 1 General 6 1 In House Repair 6 1 Storage 6 1 Periodic Tests 6 1 General 6 1 Periodic Test 6 2 SECTION 7 MANUAL CHANGE INFORMATION 7 1 ...

Page 6: ...y trip the breaker at the relay front panel Direct reading front panel controls Minimum pickup setting for safety during installation Time characteristics extend to a pickup multiple of 40 Rugged draw out construction with steel case Magnetic latching targets retain indication without power Built in accuracy eliminates internal adjustments Minimum transient overreach Field selectable instantaneous...

Page 7: ... trip 1 0 hour 1 2 times pickup Time to trip 1 0 hour 1 5 times pickup Time to trip 2 0 minutes 4 0 times pickup Time to trip 0 2 seconds 6 0 times pickup Time to trip 0 2 seconds Settings Position the following switches as designated Switch locations are shown in Section 2 Controls And Indicators Figure 1 2 is a graph showing the timing for the application scenario SW8 1 Select nominal operating ...

Page 8: ...c Curve SPECIFICATIONS BE1 50 51M 222 Overcurrent Relays have the following features and capabilities Current Sensing Input Continuous current 14 amperes One second current 400 amperes TIME PICKUP Range 0 5 to 15 9 amperes in 0 1 ampere steps Setting the TIME PICKUP to the minimum pickup 0 5 ampere places the relay in the most sensitive state and may be used as a safety setting TIME Dropout Dropou...

Page 9: ...ces the relay in the most sensitive state and may be used as a safety setting INST Dropout Dropout occurs at 95 of pickup value INST PICKUP Accuracy 2 25 milliamperes at or above 1 0 ampere settings Frequency Response A change of 5 hertz from the nominal 50 60 hertz current causes less than 0 5 change in the current required for pickup INST Transient Response Less than 10 overreach with system tim...

Page 10: ...round applications is beneficial because it helps to avoid nuisance trips For phase applications the maximum time to trip is 3 5 cycles at a pickup multiple of 1 0 and 1 5 cycles at a pickup multiple of 3 0 The corresponding times for ground applications are 4 5 and 1 75 cycles Figure 1 5 shows the instantaneous characteristic curves for maximum time to trip Additional delays of 0 1 0 2 or 0 3 sec...

Page 11: ...occur with repeating system faults Closing SW8 4 selects the integrating reset characteristic The integrating reset characteristic simulates the disk reset of electromechanical relays BE1 50 51M 222 relays provide the integrating reset function even when input current falls to zero Integrating reset characteristics are shown in Figure 1 6 Target Indicators Magnetically latched manually reset targe...

Page 12: ...res for 0 2 seconds carry 7 amperes for 2 minutes 3 amperes continuously and break 0 3 ampere Inductive 120 240 Vac Make and carry 30 amperes for 0 2 seconds carry 7 amperes for 2 125 250 Vdc minutes 3 amperes continuously and break 0 3 ampere 0 3 amperes L R 0 04 AUX Output Output contacts can be configured in the field using jumpers to select closing on either or timed or instantaneous trip Outp...

Page 13: ...es centered around 144 megahertz and 440 megahertz with the antenna located six inches from the relay in both horizontal and vertical planes Temperature Operating Range 40 C 40 F to 70 C 158 F Recommended Storage Range 50 C 58 F to 50 C 122 F Shock 15 g in each of three mutually perpendicular planes Vibration 2 g in each of three mutually perpendicular planes swept over the range of 10 to 500 hert...

Page 14: ...BE1 50 51M 222 General Information 1 9 MULTIPLES OF PICK UP Figure 1 7 Time Characteristic Curve 99 1610 Load Demand Curve ...

Page 15: ...BE1 50 51M 222 General Information 1 10 MULTIPLES OF PICK UP Figure 1 8 Time Characteristic Curve 99 1370 L Long Inverse ...

Page 16: ...BE1 50 51M 222 General Information 1 11 MULTIPLES OF PICK UP Figure 1 9 Time Characteristic Curve 99 1371 D Definite Time ...

Page 17: ...BE1 50 51M 222 General Information 1 12 MULTIPLES OF PICK UP Figure 1 10 Time Characteristic Curve 99 1372 M Moderately Inverse ...

Page 18: ...BE1 50 51M 222 General Information 1 13 MULTIPLES OF PICK UP Figure 1 11 Time Characteristic Curve I Inverse ...

Page 19: ...BE1 50 51M 222 General Information 1 14 MULTIPLES OF PICK UP Figure 1 12 Time Characteristic Curve 99 1374 V Very Inverse ...

Page 20: ...BE1 50 51M 222 General Information 1 15 MULTIPLES OF PICK UP Figure 1 13 Time Characteristic Curve 99 1375 E Extremely Inverse ...

Page 21: ...BE1 50 51M 222 General Information 1 16 MULTIPLES OF PICK UP Figure 1 14 Time Characteristic Curve B 99 1376 BS142 B ...

Page 22: ...BE1 50 51M 222 General Information 1 17 MULTIPLES OF PICK UP Figure 1 15 Time Characteristic Curve 99 1377 BS142 C ...

Page 23: ... functions or one fixed time function F TIME DIAL Selectors Two selector switches TENS and UNITS to select the desired characteristic curve A setting of 0 0 results in instantaneous operation without any intentional delay A setting of 9 9 corresponds to the typical time provided by an electromechanical relay at its maximum dial setting G TIME MANUAL TRIP Test Points When shorted the test points pr...

Page 24: ...ing reset characteristic Closing SW8 4 provides integrating reset Opening SW8 4 provides instantaneous reset K Auxiliary Output Jumper Terminations Configures the auxiliary output contacts to close with either the instantaneous 50 trip and or the timed 51 trip Jumper E2 to E1A to close the auxiliary contact with the timed 51 trip This jumper is yellow and factory installed to close the auxiliary o...

Page 25: ...BE1 50 51M 222 Controls and Indicators 2 3 Figure 2 2 BE1 50 51M 222 Location of Controls and Indicators ...

Page 26: ...ss the scaling resistors is filtered and applied to the multiplexor MUX Time Signal Current from the signal CT is also rectified and applied to the time scaling resistors controlled by the TIME PICKUP selector switches The analog voltage of the time input signal is also filtered and applied to the multiplexor Microprocessor Operating power from the power supply is applied to the microprocessor sup...

Page 27: ...e time characteristic curve If the sensed current exceeds the INST PICKUP setting the INST contacts 50 are closed Power Off Sensing The power off sensing circuits measure the decaying voltage to determine the length of time that power is removed zero current This provides information for the integrating reset function even when power has been entirely removed Outputs Instantaneous And Timed System...

Page 28: ...firmed by performing the operational test procedure in Section 5 Testing In the event the relay is not to be installed immediately store the relay in its original shipping carton in a moisture and dust free environment DIELECTRIC TEST In accordance with IEC 255 5 and IEEE C37 90 1989 one minute dielectric high potential tests may be performed as follows All circuits to ground 2828 Vdc Input to out...

Page 29: ...BE1 50 51M 222 Installation 4 2 Figure 4 1 Outline Dimensions C1 Case ...

Page 30: ...BE1 50 51M 222 Installation 4 3 Figure 4 2 Panel Drilling Diagram C1 Case ...

Page 31: ...el and part number before connecting and energizing a particular relay Connections should be made with minimum wire size of 14 AWG except as noted for the ground wire Typical ac input and dc control connections are shown in Figures 4 3 and 4 4 The auxiliary output jumper configuration schematic diagram is also shown in Figure 4 4 Relay internal connections are shown on the back of the relay Figure...

Page 32: ...BE1 50 51M 222 Installation 4 5 Figure 4 4 DC Control Connections ...

Page 33: ...BE1 50 51M 222 Installation 4 6 Figure 4 5 BE1 50 51M 222 Overcurrent Relay Rear View ...

Page 34: ...onal test procedures in this Section In the event the relay is not to be installed immediately store the relay in its original shipping carton in a moisture and dust free environment DIELECTRIC TEST In accordance with IEC 255 5 and IEEE C37 90 1989 one minute dielectric high potential tests may be performed as follows All circuits to ground 2828 Vdc Input to output circuits 2000 Vac or 2828 Vdc Ou...

Page 35: ... BE1 50 51M 9 8 7 6 5 4 2 TIME INST 3 CURRENT SOURCE INPUT STOP TIMER START AMPS TEST SET 12 08 99 D2750 21 vsd 1 0A CURRENT LIMITER TARGET CURRENT Figure 5 1 Pickup and Timing Test Setup Figure 5 2 Target Operational Test Setup ...

Page 36: ...nput current of 0 550 ampere Step 2 Decrease input current until PICKUP LED turns OFF Step 3 Set TIME PICKUP to 2 2 Step 4 Slowly increase current to terminals 8 and 9 PICKUP LED should turn ON at an input current of 2 131 to 2 269 amperes Step 5 Decrease input current until PICKUP LED turns OFF INST Pickup Test Perform preliminary setup Connect test setup as shown in Figure 5 1 Insure that SW8 sw...

Page 37: ... from when current is applied until TIME output contacts close Step 2 Apply the current step from 0 to 1 5 amperes and record the elapsed time Elapsed time should be 72 49 to 99 38 seconds This tolerance is greater than 2 because it is the accumulation of both pickup and timing tolerances Step 3 Remove input current Target Test Perform preliminary setup Connect test setup as shown in Figure 5 2 In...

Page 38: ...E MANUAL TRIP test points Check that TIME target operates Step 4 Connect a jumper between INST MANUAL TRIP test points Check that INST target operates Step 5 Reset targets Integrating Reset Test Perform preliminary setup Insure that SW8 switches are set correctly SW8 1 for operating frequency SW8 2 to OFF no instantaneous delay SW8 3 to OFF no instantaneous delay and SW8 4 to ON selects integratin...

Page 39: ...eriodic testing should consist of the following procedures Step 1 Verify that the instantaneous pickup is within 2 of the value set on the dials Pickup occurs when the INST output contacts close Step 2 Verify that the time pickup is within 2 of the value set on the dials Pickup occurs when the LED turns ON Step 3 Verify that the time to trip for the curve and time dial settings at a multiple of si...

Page 40: ...se parts may be ordered directly from Basler Electric Where special components are involved contact the Customer Service Department of the Power Systems Group Basler Electric When complete boards or assemblies are needed the following information is required 1 Relay model number 2 Relay serial number STORAGE This protective relay contains long life aluminum electrolytic capacitors Life in excess o...

Page 41: ...ngs at a multiple of six is the same as the time given on the characteristic curve Refer to Section 1 for the characteristics curves Step 4 Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater than the time given on the instantaneous characteristic curve Refer to Section 1 for the instantaneous characteristic curve Step 5 Verify that the 51 AUX contac...

Page 42: ...cerning the previous editions of the manual The substantive changes to date are summarized in the Table 7 1 Table 7 1 Changes Revision Summary of Changes ECO Date A Changed all references to the current for testing the targets to an ac only type of current Added Section 7 Manual Change Information 7480 12 20 99 ...

Reviews: