Page 1: ...INSTRUCTION MANUAL FOR NEUTRAL OVERVOLTAGE RELAY BE1 59NC P0046 15 Serial No H01234567891 NEUTRAL OVERVOLTAGE RELAY BE1 59NC Style No A1ED1JC0S1F Publication 9279400990 Revision B 09 07...

Page 2: ......

Page 3: ...ols and Indicators Functional Description Installation Testing WARNING To avoid personal injury or equipment damage only qualified personnel should perform the procedures in this manual NOTE Be sure t...

Page 4: ...peration The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electric BASLER ELECTRIC ROUTE 143 BOX...

Page 5: ...Section 7 Manual Change Information to manual introduction Added manual part number and revision to all footers Updated cover drawings Updated power supply burden data in Section 1 Updated Target Ind...

Page 6: ...iv BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...

Page 7: ...cy Recognition Certification 1 6 SECTION 2 CONTROLS AND INDICATORS 2 1 INTRODUCTION 2 1 SECTION 3 FUNCTIONAL DESCRIPTION 3 1 INTRODUCTION 3 1 FUNCTIONAL DESCRIPTION 3 1 Inputs 3 1 Filters 3 1 Overvolt...

Page 8: ...vi BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...

Page 9: ...and the circuit switcher A fault across an insulator usually means that one or more groups of parallel units are shorted This will cause a neutral shift and unbalanced phase currents Unbalanced phase...

Page 10: ...neutral relay senses this voltage unbalance and reacts to give the appropriate signal usually an alarm or trip depending on the voltage level Further loss of more capacitors increases the neutral vol...

Page 11: ...inside the case assembly The style number identification chart for the BE1 59NC relay is illustrated in Figure 1 2 Figure 1 2 Style Number Identification Chart Style Number Example If a BE1 59NC relay...

Page 12: ...ristics Inverse Response time decreases as the difference between the monitored voltage and the setpoint increases The inverse time characteristics switch is adjustable from 01 to 99 in 01 increments...

Page 13: ...circuit Continuous Rating 3 A 1 Second Rating 30 A 2 Minute Rating 7 A Type Tests Shock Withstands 15 G in each of three mutually perpendicular planes without structural damage or performance degrada...

Page 14: ...certified No POCC US ME05 B03391 complies with the relevant standards of Gosstandart of Russia Issued by accredited certification body POCC RU 0001 11ME05 CHARACTERISTIC CURVES BE1 59NC overvoltage in...

Page 15: ...9279400990 Rev B BE1 59NC General Information 1 7 Figure 1 4 Overvoltage Inverse Time Curves High Ranges...

Page 16: ...1 8 BE1 59NC General Information 9279400990 Rev B This page intentionally left blank...

Page 17: ...the controls and indicators shown and described here P0046 16 Serial No H01234567891 NEUTRAL OVERVOLTAGE RELAY BE1 59NC Style No A1ED1JC0S1F A B C D E F G H I J Figure 2 1 Location of Controls and In...

Page 18: ...oltage output delay definite timing characteristic adjustable from 00 1 to 99 9 seconds in 0 1 second increments A setting of 00 is instantaneous G POWER LED LED illuminates when proper operating powe...

Page 19: ...ltage 2 circuits are functionally the same except for timing characteristics Filters Bandpass filters provide peak sensitivity at 50 or 60 hertz for the overvoltage 1 and overvoltage 2 inputs Third ha...

Page 20: ...us relay de energizes and opens the power supply status output contacts Power Supply Operating power for the relay circuitry is supplied by a wide range electrically isolated low burden power supply P...

Page 21: ...minimum current of 200 milliamperes must flow through the output trip circuit If a wiring insulation test is required remove the connection plugs and withdraw the relay from its case MOUNTING Because...

Page 22: ...4 2 BE1 59NC Installation 9279400990 Rev B Figure 4 1 Panel Cutting Drilling Semi Flush Case...

Page 23: ...9279400990 Rev B BE1 59NC Installation 4 3 Figure 4 2 Panel Cutting Drilling Double Ended Projection Mount Case...

Page 24: ...4 4 BE1 59NC Installation 9279400990 Rev B D1427 27 12 04 01 Figure 4 3 Case Dimensions Side View Double Ended Semi Flush Case...

Page 25: ...9279400990 Rev B BE1 59NC Installation 4 5 Figure 4 4 Case Dimensions Side View Double Ended Projection Mount Case...

Page 26: ...4 6 BE1 59NC Installation 9279400990 Rev B Figure 4 5 Case Dimensions Rear View Semi Flush Case...

Page 27: ...9279400990 Rev B BE1 59NC Installation 4 7 Figure 4 6 Case Dimensions Rear View Projection Mount Case...

Page 28: ...4 8 BE1 59NC Installation 9279400990 Rev B P0002 12 01 31 01 Figure 4 7 Case Cover Dimensions Front View...

Page 29: ...relay Incorrect wiring may result in damage to the relay Except where noted connections should be made with wire no smaller than 14 AWG Typical control circuit connections are shown in Figure 4 8 Typi...

Page 30: ...4 10 BE1 59NC Installation 9279400990 Rev B Figure 4 9 Typical Protection Methods...

Page 31: ...9279400990 Rev B BE1 59NC Installation 4 11 Figure 4 10 Typical Internal Connections...

Page 32: ...Basler Electric to coordinate repairs STORAGE This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in excess of 10 years at storage temperatures less...

Page 33: ...lowly turn OVERVOLTAGE 1 PICKUP adjust potentiometer R63 CCW until OVERVOLTAGE 1 PICKUP LED just illuminates Step 3 Set OVERVOLTAGE 1 TIME DIAL to 001 and apply to case terminals 6 and 7 a voltage tha...

Page 34: ...rvoltage at case terminals 6 and 7 Observe the time registered by the counter Time must equal the setting 100 milliseconds or 2 whichever is greater Step 13 Set OVERVOLTAGE 2 TIME DIAL to 100 Monitor...

Page 35: ...OVERVOLTAGE 1 TIME DIAL to 11 Step 5 Reset the timer Turn on PS1 While monitoring the output terminals indicated in Figure 5 1 for OVERVOLTAGE 1 initiate PS2 and record the time delay Verify that the...

Page 36: ...d in Figure 5 1 for OVERVOLTAGE 2 Remove and then reapply the overvoltage at case terminals 6 and 7 Observe the time registered by the counter Time must equal the setting 100 milliseconds or 2 whichev...

Page 37: ...conds whichever is greater of the time shown in Table 5 1 Step 12 Remove PS1 and PS2 voltage Step 13 With reference to Figure 5 2 set PS1 for the value shown in Table 5 1 and for the specific input op...

Page 38: ...5 6 BE1 59NC Testing 9279400990 Rev B This page intentionally left blank...