6-2
BE1-79A Testing
9310200990 Rev G
4. Place Test switch S1 in the 52a position and observe that after five seconds, the front panel Reset
LED and Reset indicator L1 light.
5. Place Test switch S1 in the 52b position. When Reclose indicator L2 lights, momentarily place Test
switch S1 in the 52a position and verify that L2 turns off.
6. Place Test switch S1 in the 52b position and verify that after 10 seconds, L2 lights for three seconds.
7. Place Test switch S1 in the 52a position and verify that after 15 seconds, the front panel Reset LED
and Reset Indicator L1 light.
DELAYED RECLOSE TESTING
ACR11A Style
Place Style Configuration switches S1, S2, and S3 in the A position. Place Instantaneous Reclose
Jumper switch S4 in the EXT position. Place RS Contact switch S5 in the NO position.
ACR11B Style
Place Style Configuration switches S1, S2, and S3 in the B position. Place Instantaneous Reclose
Jumper switch S4 in the EXT position. Place RS Contact switch S5 in the NO position.
ACR11A and ACR11B Styles
1. Place Test switch S1 in the 52a position and apply 120 Vac to the relay and test circuit.
2. Connect a PC with a serial port and suitable communication software to the relay serial port. Transmit
the settings of Table 6-2 to the relay. (These settings correspond to the illustration of Figure 3-5.)
Table 6-2. Delayed Reclose Testing Commands
Command
Time Between Recloses
ACCESS=<cr> N/A
SP-79A1=10.0,20.0<cr>
10 – 0 = 10 s
SP-79A2=30.0,40.0<cr>
30 – 10 = 20 s
SP-79A3=50.0,60.0<cr>
50 – 30 = 20 s
SP-79A4=70.0,80.0 <cr>
70 – 50 = 20 s
SP-79ALO=180,185<cr>
180 – 70 = 110 s
SP-79ARS=D,10,9<cr> N/A
EXIT<cr> N/A
Y<cr> N/A
3. Place Test switch S1 in the 52b position and observe that the following sequence of events occur.
a. Front panel Reset LED turns off
b. Reset indicator L1 turns off
c. Front panel In Sequence LED lights
d. After 10 seconds, Reclose indicator L2 will light for three seconds
e. After 30 seconds, L2 will light for three seconds
f. After 50 seconds, L2 will light for three seconds
g. After 70 seconds, L2 will light for three seconds
h. After 180 seconds, the front panel Lockout led and Lockout indicator L3 will light
4. Place Test switch S1 in the 52a position and observe that after five seconds, the front panel Reset
LED and Reset indicator L1 light.
5. Place Test switch S1 in the 52b position. When Reclose indicator L2 lights 10 seconds later, place S1
in the 52a position momentarily and verify that Reclose indicator L2 turns off.
6. Place Test switch S1 in the 52b position before 20 seconds elapse and verify that after 30 seconds,
Reclose indicator L2 lights for three seconds.
7. Place Test switch S1 in the 52a position and verify that after 40 seconds, the front panel Reset LED
and Reset indicator L1 light.
Summary of Contents for BE1-79A
Page 1: ...INSTRUCTION MANUAL FOR RECLOSING RELAY BE1 79A Publication 9310200990 Revision G 02 08...
Page 2: ......
Page 8: ...vi BE1 79A Introduction 9310200990 Rev G This page intentionally left blank...
Page 10: ...ii BE1 79A General Information 9310200990 Rev G This page intentionally left blank...
Page 16: ...ii BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 20: ...2 4 BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 22: ...ii BE1 79A Functional Description 9310200990 Rev G This page intentionally left blank...
Page 34: ...ii BE1 79A Communication Commands 9310200990 Rev G This page intentionally left blank...
Page 40: ...ii BE1 79A Installation and Configuration 9310200990 Rev G This page intentionally left blank...
Page 52: ...ii BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 58: ...6 6 BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 60: ...ii BE1 79A RS Contact Application 9310200990 Rev G This page intentionally left blank...
Page 66: ...ii BE1 79A Terminal Communication 9310200990 Rev G This page intentionally left blank...