9310200990 Rev G
BE1-79A Functional Description
3-1
SECTION 3
•
FUNCTIONAL DESCRIPTION
INTRODUCTION
BE1-79A relays are microprocessor-based devices that provide automatic reclosing of circuit breakers.
This section describes the hardware, circuitry, and software of the BE1-79A.
HARDWARE
The BE1-79A is supplied as an S1 cradle and case (200 series) or an S2 cradle without a case (100
series).
100 Series Description
The BE1-79A-100 and –101 consist of a draw-out cradle assembly that is intended for installation in an
existing S2 case. A case is not provided with the cradle assembly.
200 Series Description
The BE1-79A-200 and –201 consist of a draw-out cradle assembly with a steel and phenolic case. The
case has the same overall dimensions as a Basler Electric or General Electric S1 case.
CIRCUIT OPERATION
This description of circuit operation is divided into
Inputs
,
Microprocessor
, and
Outputs
. BE1-79A circuit
functions are illustrated in Figure 3-1 and described in the following paragraphs.
V1
V3
V2
V4
V5
MICROPROCESSOR
C1
C3
C5
C7
C9
ISO
ISO
ISO
ISO
ISO
EEPROM
Settings and Status
Memory
RAM
Operating
Memory
ROM
Program
Memory
AC/DC
Power
Reset
Watchdog
Timer Circuit
Power Supply
RS-232
LED
Indicators
D2588-04
08-17-05
C2
C4
C6
C10
C8
S5
Figure 3-1. Function Block Diagram
Inputs
The four types of BE1-79A inputs are:
•
Operating
power
•
Contact sensing inputs
•
Reset
switch
•
Serial communication port
Summary of Contents for BE1-79A
Page 1: ...INSTRUCTION MANUAL FOR RECLOSING RELAY BE1 79A Publication 9310200990 Revision G 02 08...
Page 2: ......
Page 8: ...vi BE1 79A Introduction 9310200990 Rev G This page intentionally left blank...
Page 10: ...ii BE1 79A General Information 9310200990 Rev G This page intentionally left blank...
Page 16: ...ii BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 20: ...2 4 BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 22: ...ii BE1 79A Functional Description 9310200990 Rev G This page intentionally left blank...
Page 34: ...ii BE1 79A Communication Commands 9310200990 Rev G This page intentionally left blank...
Page 40: ...ii BE1 79A Installation and Configuration 9310200990 Rev G This page intentionally left blank...
Page 52: ...ii BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 58: ...6 6 BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 60: ...ii BE1 79A RS Contact Application 9310200990 Rev G This page intentionally left blank...
Page 66: ...ii BE1 79A Terminal Communication 9310200990 Rev G This page intentionally left blank...