background image

2-2

BE1-79S Functional Description

Figure 2-1. Functional Block Diagram

POWER SUPPLY

Basler Electric enhanced the power supply design for unit case relays.  This new design created three, wide
range power supplies that replace the four previous power supplies.  Style number identifiers for these
power supplies have not been changed so that customers may order the same style numbers that they
ordered previously.  The first newly designed power supplies were installed in unit case relays with EIA date
codes 9638 (third week of September 1996).   Relays with a serial number that consists of one alpha
character followed by eight numerical characters also have the wide range power supplies.  A benefit of this
new design increases the power supply operating ranges such that the 48/125 volt selector is no longer
necessary.  Specific voltage ranges for the three new power supplies and a cross reference to the style
number identifiers are shown in the following table.

Table 2-1. Wide Range Power Supply Voltage Ranges

Power Supply

Style Chart Identifiers

Nominal Voltage

Voltage Range

Low Range

D

24 Vdc

12† to 32 Vdc

Mid Range

B, C 

48, 125 Vdc,

120 Vac

24 to 150 Vdc,

90 to 132 Vac

High Range

X

125, 250 Vdc,

120, 240 Vac

62 to 280 Vdc,

90 to 270 Vac

† 14 Vdc is required to start the power supply.

Relay operating power is developed by the wide range, isolated, low burden, flyback switching, solid state
power supply.  Nominal ±12 Vdc is delivered to the relay internal circuitry.  Input (source voltage) for the
power supply is not polarity sensitive.  A red LED turns ON to indicate that the power supply is functioning
properly. 

INITIATE CONTACT SENSING (RI)

When an external form A contact (RI) is closed (typically by a protective relay), the initiate contact sensing
circuit generates an INITIATE signal to the automatic reclose enable logic.

Summary of Contents for BE1-79S

Page 1: ...INSTRUCTION MANUAL FOR SINGLE SHOT RECLOSING RELAY BE1 79S Publication Number 9 1410 00 990 Revision B 02 2001...

Page 2: ...ould perform the procedures presented in this manual INTRODUCTION This Instruction Manual provides information concerning the operation and installation of BE1 79S Single Shot Reclosing Relay To accom...

Page 3: ...tric Co Highland IL 62249 February 2001 It is not the intention of this manual to cover all details and variations in equipment nor does this manual provide data for every possible contingency regardi...

Page 4: ...c 2 3 Reclose Timer 2 3 Reclose Fail Timer 2 3 Reset Timer 2 3 Voltage Monitor 2 4 Power Supply Output 2 7 SECTION 3 HUMAN MACHINE INTERFACE 3 1 Controls and Indicators 3 1 Switches 3 4 SECTION 4 INST...

Page 5: ...ng closed for the reset interval Automatic reclosing of a tripped breaker requires that a reclose initiate signal RI be generated by the protective system and received by the reclosing relay prior to...

Page 6: ...side the case assembly Upon receipt of a reclosing relay be sure to check relay style number against the requistion and packing list to see that they agree Style Number Example The Style Number Identi...

Page 7: ...ble 1 1 Power Supplies Type Nominal Input Voltage Input Voltage Range Burden at Nominal B Mid Range 48 Vdc 24 to 150 Vdc 5 5 W C Mid Range 125 Vdc 120 Vac 24 to 150 Vdc 90 to 132 Vac 4 0 W 10 0 VA D L...

Page 8: ...polarity sensitive and requires 24 60 Vdc at a burden of 3 5 W for a Type B power supply 62 150 Vdc at 4 5 W for a Type C power supply 12 32 Vdc at 2 0 W for a Type D power supply and 140 280 Vdc at...

Page 9: ...uracy Either 95 10 0 seconds with Reset Timer B or 15 2 0 seconds with Reset Timer C for a nominal input frequency of 50 60 Hz at 25 C Non adjustable Temperature Operating Temperature Storage Temperat...

Page 10: ...bus and dead line dead bus reclosing conditions The reclosing conditions voltage levels are established by adjustable controls on the front panel LB DB OV LL and DL OV The overvoltage limit OV mode a...

Page 11: ...necessary Specific voltage ranges for the three new power supplies and a cross reference to the style number identifiers are shown in the following table Table 2 1 Wide Range Power Supply Voltage Rang...

Page 12: ...s expired Option 3 2 or 3 3 RECLOSE FAIL TIMER Option 3 2 or 3 3 A RECLOSE FAIL signal is generated by the reclose fail timer if the reclose command from the relay does not cause the controlled breake...

Page 13: ...ls for the line and bus inputs over the range of 10 to 135 volts This scheme establishes precise voltage conditions under which reclosing can occur Non selection of specific closing conditions prevent...

Page 14: ...BE1 79S Functional Description 2 5 Figure 1 1 Figure 2 2 Voltage Monitor Conditions Modes and Voltage Levels Diagram Option 2 D or 2 S Only...

Page 15: ...bus are provided by the dual function front panel controls DL OV and DB OV When the situation occurs in which both a live zone and a dead zone are elected and OV is selected for the live zone the dea...

Page 16: ...relay is energized and its NC output contact is opened when power is applied to the relay Normal internal relay operating voltage maintains the power supply status output relay continuously energized...

Page 17: ...BE1 79S Human Machine Interface 3 3 Figure 3 1 Location of Controls and Indicators Figure 3 2 Optional Voltage Monitor Board CONDITION and MODE Switches Location...

Page 18: ...less than the overvoltage limit setting during the overvoltage limit mode E DB OV Control Option 2 S D This multi turn screw accessible through the front panel provides continuous selection over a ran...

Page 19: ...This multi turn screw accessible through the front panel provides continuous selection over a range of 10 to 135 volts of the live line voltage monitoring level Adjustment is by small screwdriver Min...

Page 20: ...BE1 79S Human Machine Interface 3 3 Figure 3 1 Location of Controls and Indicators Figure 3 2 Optional Voltage Monitor Board CONDITION and MODE Switches Location...

Page 21: ...on disables live line dead bus reclosing On down position enables live line dead bus reclosing CONDITION Switch No 5 Option 2 S D Off up position disables dead line dead bus reclosing On down position...

Page 22: ...lay model and style number against the requisition and packing list to see that they agree MOUNTING The relay is intended to be vertically mounted in a location relatively free of moisture dust and ex...

Page 23: ...torage life can be extended if at 1 one year intervals power is applied to the relay for a period of 30 thirty minutes 2 02 01 D1427 01 Removal of the connecting plugs opens the reclosing contact and...

Page 24: ...ETAIL A A SHOWING THE ADDITION OF WASHERS OVER THE BOSS TO TIGHTEN THE RELAY AGAINST THE PANEL CAS E Figure 4 2 S1 Case Double Ended Semi Flush Mounting Outline Dimensions Side View Figure 4 3 S1 Case...

Page 25: ...4 4 BE1 79S Installation Figure 4 4 S1 Case Double Ended Projection Mount Outline Dimensions Rear View...

Page 26: ...BE1 79S Installation 4 5 Figure 4 5 S1 Case Panel Drilling Diagram Semi Flush Mounting...

Page 27: ...4 6 BE1 79S Installation Figure 4 6 S1 Case Double Ended Projection Mounting Panel Drilling Diagram Rear View Figure 4 7 Control Circuit Connections Typical...

Page 28: ...BE1 79S Installation 4 7 Figure 4 8 Voltage Sensing Circuit Connections...

Page 29: ...4 8 BE1 79S Installation Figure 4 9 RI RC and 52b Sensing Circuit Connections...

Page 30: ...BE1 79S Installation 4 9 Figure 4 10 Internal Connection Diagram With Power Supply Status...

Page 31: ...5 2 If equipped with Power Supply Status Output Option 2 F and with the unit in a powered up condition verify that the power supply status output contact is energized open terminals 11 and 16 Remove...

Page 32: ...5 2 BE1 79S Operational Test Figure 5 1 Test Setup Diagram Typical Figure 5 2 Test Setup Diagram Voltage Monitor Option 2 S D...

Page 33: ...ess to the voltage monitor board CONDITION and MODE switches remove the connecting plugs and remove the cradle assembly from the relay Step 15 Select the LL DB condition by setting CONDITION switch no...

Page 34: ...50 and 150 milliseconds Step 29 About one minute after S2 was depressed LOCKOUT LED goes out and RESET LED lights Step 30 Set RECLOSE TIME fully clockwise 2 seconds to test maximum reclose time operat...

Page 35: ...and RESET LED lights Step 46 Press and release S2 and immediately press S3 to simulate a breaker trip followed by an RC signal Step 47 Observe RESET LED goes out No automatic reclosure occurs Step 48...

Page 36: ...ead line dead bus condition set CONDITION switch no 5 to the on down position Step 4 To select the overvoltage limit OV mode for the live line and or live bus conditions perform one or both of the fol...

Page 37: ...tions until the associated indicator just lights To check the operation of the relay with the resulting set up perform the following steps Step 11 Momentarily press switch S1 to energize relay K1 Step...

Page 38: ...operational check The procedures in Section 5 of this manual provide an adequate check to verify proper operation of the relay If the relay fails to function and factory repair is desired contact the...

Page 39: ...Option 3 from 0 None to 0 No reclose fail timer continuous reclose output until breaker closes Added Option 2 D when Option 2 S is referred to in the manual Added new power supply information to Spec...

Reviews: