BE1-951
Protection and Control
4-59
SL-86/186 Command
Purpose:
Read/Set Logic for 86 Function Modules
Syntax: SL-<x>86[=<mode>,<Trip>,<Reset>]
Comments: x= nothing for 86 and 1 for 186.
SL-86 Command Example:
1.
Enable the relay to trip when an overcurrent fault occurs and reset when virtual switch 143 is pressed.
>SL-86=1,50TP+50TN+50TQ+51P+51N+51Q, 143