BE1-951
Testing and Maintenance
13-13
Energy Data and Demand
Read, change or reset KWH and KVARH records. If the Demand Functions feature of the relay is enabled,
use the following to reset the peak current, watt, and var demand registers to "0" or a pre-existing value:
Reference Commands: RE, RD, RD-<pp>
Reference HMI Screens: 4.4.1.x, 4.4.2.x, 4.4.3.x
Refer to Section 6,
Energy Data and Demand Functions, for setting details.
Breaker Monitoring
If the Breaker Monitoring features of the relay are enabled, use the following to reset the counter and the
duty registers to "0" or a pre-existing value:
Reference Commands: RB-OPCNTR, RB-DUTY
Reference HMI Screens: 4.3.1
Refer to Section 6,
Breaker Monitoring, for setting details.
Relay Trouble Alarms
Reset and verify that the relay trouble alarm is not illuminated. If required, alarm information can be read
by transmitting the RA or RG-STAT commands. To attempt clearing a Relay Trouble Alarm, first gain write
access to the reporting functions ("R" password) and initiate the RA=0 or RA-REL=0 commands, or press
the RESET key from a STAT \ALARMS \ALARM screen on the HMI. Refer to Section 6,
Relay Trouble
Alarms, for setting details.
Major/Minor/Logic Programmable Alarms
Reset and verify that the programmable alarms, Major, Minor, and Logic, as set to meet user needs, are not
illuminated or asserted. If required, alarm information can be read by transmitting the RA or RG-STAT
commands. To reset a Major/Minor/Logic Alarm, first gain write access to the reporting functions ("R"
password) and initiate the RA=0 or RA-MAJ/MIN/LGC=0 commands, or by pressing the RESET key from
a STAT \ALARMS \DET screen on the HMI.
Refer to Section 6,
Major/Minor/Logic Programmable Alarms, for setting details.
Targets
Reset and verify that there is no target information. Targets are reset from HMI screen 1.1.1, \STATS
\TARGETS by pressing the RESET key, or gaining write access to the reporting functions ("R" password)
and transmitting RG-TARG [= 0]. Relay target information can be read either from HMI screen 1.1.1, \STATS
\TARGETS, or by transmitting the RG-TARG command.
Refer to Section 6,
Targets, for setting details.
Fault Summary Reports
Reset "new" fault summary directory records to "0" by first gaining write access to the reporting functions
("R" password), and transmitting the RF-NEW [= 0] command. Verify that new faults is "0" by transmitting
the RF command.
Refer to Section 6,
Fault Summary Reports, for setting details.
Sequence of Events Recorder (SER)
Reset the "new" SER records counter to "0" by first gaining write access to the reporting functions ("R"
password), and transmitting the RS-NEW [= 0] command two times. Verify that new records is "0" by
transmitting the RS command.
Refer to Section 6,
Sequence of Events Recorder Function, for setting details.