BE1-951
Security
9-1
SECTION 9 • SECURITY
INTRODUCTION
Security, in the form of multilevel password protection, is discussed along with the information required for
protecting specific function groups and user interface components against unauthorized access.
Passwords provide access security for three distinct functional access areas: Settings, Reports, and Control.
Each functional area can be assigned a unique password or one password can be assigned to multiple
areas. A global password is used to access all three of the functional areas. BE1-951 passwords are not
case sensitive; either lowercase or uppercase letters may be entered. Password security only limits write
operations; passwords are never required to read information from any area.
Additional security is provided by controlling the functional areas that can be accessed from a particular
communication port. For example, security can be configured so that access to Control commands from the
rear RS-232 port (COM1) is denied. Then, an attempt to issue a Control command through COM1 will cause
the relay to respond with an ACCESS DENIED and/or INVALID PASSWORD message. This will occur
whether a valid password is entered or not. When configuring communication port access areas, you should
be aware that the front RS-232 port (COM0) and the front panel HMI are treated as the same port.
The communication ports and password parameters act as a two-dimension control to limit changes. For
a command to be accepted, the entered password must be correct and the command must be entered
through a valid port. Only one password can be active at one time for any area or port. For example, if a
user gains write access at COM1, then users at other areas (COM0, front panel HMI, and COM2) won’t be
able to gain write access until the user at COM1 uses the EXIT command to release access control.
If a port holding access privileges, sees no activity (command entered or HMI key pressed) for approximately
five minutes, access privileges and any pending changes will be lost. This feature ensures that password
protection can’t be accidentally left in a state where access privileges are enabled for one area and other
areas locked out for an indefinite period.
If password protection is disabled, then entering ACCESS= followed by no password or any alphanumeric
character string will obtain access to the unprotected area(s).
Setting Up Password Protection
Password protection is configured for each access area port and communication port with the GS-PW
(Global Security-PassWord) command. Password protection settings are summarized in Table 1-1.
If the relay is ordered with an advanced protocol, security parameters accessed by COM2 may not apply.
See the appropriate protocol manual for details.
Table 9-1. Password Protection Settings
Setting
Range/Purpose
password
User defined alphanumeric string with a maximum of 8 characters
A setting of 0 disables password protection.
com
ports
0 = Front RS-232 port
1 = Rear RS-232 port
2 = Rear RS-485 port
Multiple ports may be selected by using
a slash (/) between each port
designator.