BE1-BPR
SPECIFICATIONS
7
AC CURRENT INPUT
5A CT: 20A continuous, 400A for one second
1A CT: 4A continuous, 80A for 1 second
OVERCURRENT DETECTORS
Three are provided and may be set up for
3-phase or neutral
INSTANTANEOUS OC PICKUP RANGE
5A CT: 0.25 to 9.99 amperes in 0.01 steps
1A CT: 0.05 to 2.00 amperes in 0.01 steps
AVERAGING OC PICKUP RANGE
5A CT: 0.05 to 1.00 amperes in 0.01 steps
1A CT: 0.01 to 0.20 amperes in 0.01 steps
OVERCURRENT PICKUP TIME
21 ms maximum @ 60 Hz
OVERCURRENT DROP OUT TIME
4.2 ms @ 60 Hz
OSCILLOGRAPHIC RECORDING RANGE
5A CT: 0 to 200 amperes, RMS
1A CT: 0 to 40 amperes, RMS
OSCILLOGRAPHIC RECORDING
12 samples per cycle in COMTRADE format
TIMERS, Standard
Six microprocessor controlled timers
adjustable from 10 to 999 ms in 1 ms steps,
or 1 to 60 sec in 0.1 sec steps, or 1-3600 cycles
in 1 cycle steps
REAL TIME CLOCK
Resolution:
±
1 sec
Stability:
±
30ppm typical
INPUT CONTACT SENSING RANGE
Within DC power supply input rating range
Programmable recognition time, 4-255 ms
OUTPUT RELAY SPEED
4 ms typical, 5 ms maximum on Output #1
8 ms typical, 10 ms maximum on Outputs #2-5
DISPLAY
2 line x 16 character backlit LCD display
OUTPUT CONTACT RATINGS
120/240Vac: Make and carry 30 A for 0.2 sec,
carry 7 A continuously and break 7A.
250Vdc: Make and carry 30A for 0.2 sec,
carry 7A continuously and break 0.3A
TARGETS
Five diagnostic LEDs are provided plus
target display of all I/O contacts
COMMUNICATIONS
Includes front and rear RS-232 ports and a
rear RS-485 port. Only one port can be active at
a time.
Oscillographic records conform to IEEE C37.111-
1991
IEEE Standard Common Format for
Transient Data Exchange (COMTRADE) for Power
Systems. Protocol: ASCII or binary data
transmissions.
BESTview for Windows
™
is a free software
application program that enables communication
between PCs and BE1-BPR relays. Through
BESTview, you can retrieve and display
COMTRADE oscillographic fault data, access the
front panel from a remote location to change
settings, retrieve a computer file of the relay
settings, or send a computer file to the relay
to perform all relay settings.
RADIO FREQUENCY INTERFERENCE
Field tested using a five watt tranceiver from
144 to 440 MHz
POWER SUPPLIES
48/125 V: 40 to 150 Vdc, 100 to 130Vac
125/250 V: 90 to 300 Vdc, 200 to 260Vac
MECHANICAL
OPERATING TEMPERATURE
-40°C to +70°C (-40°F to +158°F)
VIBRATION
2g over the range of 10 to 500 Hz
CASE SIZE (Vertical unit)
M1 case size
6.61”W x 16.2”H x 9.45”D behind panel
CASE SIZE (Horizontal unit)
Nineteen inch rack mount
19”W x 3.48”H x 9.4”D behind panel
or 8.4”D with movable flanges
WEIGHT
12 pounds maximum.