BE1-BPR Communications
6-5
The following paragraphs briefly summarize the function and syntax of each command and provide a
reference where more detailed information can be found.
ACCESS Command
Purpose:
Reads or changes access area so that programming or settings changes can be made.
Syntax:
ACCESS[=<password>]
Reference:
Section 4,
Functional Description, Software Functional Description, Changing Parameters
Using Communication Ports
BKRCON Command
(Enhanced Relays Only)
Purpose:
Reads or changes data on the breaker contacts used by breaker diagnostic routines.
Syntax:
BKRCON[=<DMAX>,<Tc>,<Ti>]
Reference:
Section 4,
Functional Description, Software Functional Description, Breaker Status, Breaker
Contact Duty Diagnostics (Enhanced Relays Only)
BKROPS Command
Purpose:
Reads or changes breaker operations data.
Syntax:
BKROPS[=<#operations>,<52a/b contact logic>]
Reference:
Section 4,
Functional Description, Software Functional Description, Breaker Status,
Breaker Status Screens
BKRRES Command
Purpose:
Reads or changes data on the breaker resistor used by breaker diagnostic routines.
Syntax:
BKRRES[=<MAXOPS>,<reset>,<Ires>]
Reference:
Section 4,
Functional Description, Software Functional Description, Breaker Status,
Breaker Resistor Diagnostics
CAL Command
Purpose:
Read or change calibration values.
Syntax:
CAL[x][=<amps>]
Reference:
Section 4,
Functional Description, Software Functional Description, Maintenance,
Calibrating the Analog Channels
COM Command
Purpose:
Reads or changes the communications protocol
Syntax:
COM[x][=<ratedps>][,Ay][,Ey][,Hy][,Pyy][Xy]
Reference:
Section 4,
Functional Description, Software Functional Description, Maintenance,
Communication Settings
CT Command
Purpose:
Reads or changes the current transformer ration settings.
Syntax:
CT[t][=<ratio>]
Reference:
Section 4,
Functional Description, Relay Setup, Transformer Ratios
DATE Command
Purpose:
Reads or changes the date setting.
Syntax:
DATE[=<dm>/<md>/<yr>]
Reference:
Section 4,
Functional Description, Maintenance, Time and Date
DIAG Command
Purpose:
Reads or resets diagnostic information.
Syntax:
DIAG[=0]
Reference:
Section 4,
Functional Description, Relay Status
DLOG Command
(Enhanced Relays Only)
Purpose:
Reads or changes breaker contact duty log data.
Syntax:
DLOG[P][=<YY>]
Reference:
Section 4,
Functional Description, Breaker Status, Breaker Contact Duty Diagnostics
(Enhanced Relays Only)
FLOG Command
(Enhanced Relays Only)
Summary of Contents for BE1-BPR
Page 31: ...BE1 BPR Application 2 17...
Page 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Page 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Page 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Page 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Page 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Page 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Page 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Page 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...