BE1-BPR General Information
1-5
Table 1-2. BE1-BPR Relays, One-Ampere Secondary
Part Number
Options
Mounting Style
IRIG-B
Power Supply
9 2720 00 304
Standard
19" Rack Mount
Yes
48/125 V ac/dc
9 2720 00 305
Standard
19" Rack Mount
Yes
125/250 V ac/dc
9 2720 00 306
Enhanced
19" Rack Mount
Yes
48/125 V ac/dc
9 2720 00 307
Enhanced
19" Rack Mount
Yes
125/250 V ac/dc
SPECIFICATIONS
BE1-BPR Breaker Protection Relays have the following features and capabilities.
Current Sensing
Four isolated inputs with a maximum burden of less than 0.1 ohm.
5 Ampere CT
Maximum continuous current: 20 amperes. Maximum one second current:
500 amperes.
1 Ampere CT
Maximum continuous current: 4 amperes. Maximum one second current:
80 amperes.
Current Detector
Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3):
Pickup Time
1¼ cycle maximum for current 125% greater than pickup.
Moving Average Window Fault Detector (50/60 Hz RMS Filter Type 2):
Maximum pickup time is (Window_size/C_PM + 1¼(cy)), where
Window_size = Filter window size in cycles (Range 1 - 100) and C_PM =
Current Pickup Multiple
Current Detector
Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3):
Dropout Time
Dropout/pickup ratio: 90%, typical. One-quarter cycle (4.2 milliseconds @
60 hertz) from the time the current falls below and stays below 25% of the
RMS level or 1¼ cycle from the time the RMS current signal decreases to
less than 75% of pickup.
Moving Average Window Fault Detector
(50/60 Hz RMS Filter Type 2):
Maximum dropout time is (Window_size-(Window_size/C_PM) +1¼ (cy)),
where Window_size = Filter window size in cycles (Range 1 - 100) and
C_PM = Current Pickup Multiple level before dropout.
Current Pickup Range
Three independent settings, selectable as three-phase or neutral
Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3):
(5 ampere CT) - 0.25 to 9.99 amperes selectable in 0.01 increments
(1 ampere CT) - 0.05 to 2.00 amperes selectable in 0.01 increments
Moving Average Window Fault Detector
(50/60 Hz RMS Filter Type 2):
(5 ampere CT) - 0.05 to 1.00 amperes selectable in 0.01 increments
(1 ampere CT) - 0.01 to 0.20 amperes selectable in 0.01 increments
Current Pickup Accuracy
Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3):
(5 ampere CT) - ±2% of pickup setting or ±0.05 ampere (whichever is
greater)
(1 ampere CT) - ±2% of pickup setting or ±0.01 ampere (whichever is
greater)
Summary of Contents for BE1-BPR
Page 31: ...BE1 BPR Application 2 17...
Page 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Page 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Page 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Page 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Page 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Page 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Page 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Page 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...