1-8
BE1-BPR General Information
Protocol:
ASCII and binary data transmissions
Power Supply
Power for the internal circuitry may be derived from ac or dc external power
sources and is provided in Table 1-4.
Table 1-4. Power Supply Specifications
Power
Supply
Range
Nominal
Input
Voltage
Input Voltage
Range
Burden at
Nominal
(Maximum
48/125 V
48 Vdc
125 Vdc
120 Vac
40 to 60 Vdc
90 to 150 Vdc
100 to 130 Vac
8 W (10 W)
8 W (10 W)
8 W (10 W)
125/250 V
125 Vdc
120 Vac
250 Vdc
240 Vac
90 to 150 Vdc
100 to 130 Vac
180 to 300 Vdc
200 to 260 Vac
8 W (10 W)
8 W (10 W)
8 W (10 W)
8 W (10 W)
Isolation
All output and power supply terminals have MOV suppressors. Maximum
applied voltage must be no greater than 300 volts where MOV suppressors
are used. Surge suppression capacitors are installed between terminal
pairs and between terminals and chassis ground. When testing with 1,500
Vac, leakage current (approximately 8 milliamperes per terminal) is
expected. 1,500 Vac (RMS) at 45 to 65 hertz for one minute or 2,121 Vdc
may be applied between circuit groups, and between circuit groupt and
chassis ground in accordance with IEC 255-5 and ANSI/IEEE C37.90-1989
(Dielectric Tests).
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989,
Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay Systems. Note:
this qualification does not include the front RS-232 communication port.
Radio Frequency
Interference (RFI)
Field tested using a five watt, hand held transceiver operating at random
frequencies centered around 144 megahertz and 440 megahertz, with the
antenna allocated six inches from the relay in both horizontal and vertical
planes.
Operating Temperature
-40
(
C (-40
(
F) to +70
(
C (+158
(
F)
Storage Temperature
-40
(
C (-40
(
F) to +70
(
C (+158
(
F)
Shock
Type tested to withstand 15 g in each of three mutually perpendicular
planes, swept over the range of 10 to 500 Hz for a total of 6 sweeps, 15
minutes each sweep, without structural damage or degradation of
performance.
Vibration
Type tested to withstand 2 g in each of three mutually perpendicular planes,
swept over the range of 10 to 500 Hz for a total of 6 sweeps, 15 minutes
each sweep, without structural damage or degradation of performance.
Weight
12 pounds maximum
Summary of Contents for BE1-BPR
Page 31: ...BE1 BPR Application 2 17...
Page 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Page 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Page 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Page 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Page 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Page 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Page 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Page 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...